A–10 Setting Up the DH-485 Network<br />

Important: The SLC 500 Series A (only) processors set the<br />

maximum node address to 31 when power is cycled<br />

increasing initialization and response time of the<br />

network.<br />

Maximum Number of Communicating Devices<br />

SLC 500 fixed and SLC 5/01 processors can be selected by two<br />

initiators maximum at the same time. Using more than two initiators<br />

to select the same SLC 500 fixed and SLC 5/01 processors at the<br />

same time can cause communication timeouts.<br />

Installing the DH-485<br />

Network<br />

To install a DH-485 network, you will need tools to strip the shielded<br />

cable and to attach the cable and terminators to the Isolated Link<br />

Coupler.<br />

Install the DH-485 network using the following tools (or equivalent):<br />

Description Part Number Manufacturer<br />

Shielded Twisted Pair<br />

Belden #3106A or #9842 Belden<br />

Cable<br />

Stripping Tool 45-164 Ideal Industries<br />

1/8 ” Slotted Screwdriver Not Applicable Not Applicable<br />

DH-485 Communication Cable and Isolated Link Coupler<br />

The link coupler provides a connection for each node. The isolated<br />

link coupler electrically isolates the DH-485 communication<br />

interface from the processor and peripheral connections.<br />

Electrical-optical isolation is provided to 1500V.<br />

The suggested DH-485 communication cable is Belden #3106A or<br />

#9842 cable. The cable is jacketed and shielded with two twisted<br />

wire pairs and a drain wire.<br />

One pair provides a balanced signal line, and one wire of the other<br />

pair is used for a common reference line between all nodes on the<br />

network. The shield reduces the effect of electrostatic noise from the<br />

industrial environment on the network communication.<br />

Installing the DH-485 Communication Cable<br />

The communication cable consists of a number of cable segments<br />

daisy-chained together. The total length of the cable segments<br />

cannot exceed 1219 m (4000 ft).<br />

Publication <strong>1747</strong>-6.2