System Installation Recommendations<br />
3–9<br />
!<br />
ATTENTION: Your SLC 500 power supply can be<br />
damaged by voltage surges when switching inductive<br />
loads such as motors, motor starters, solenoids, and<br />
relays. To avoid damage to your SLC 500 power<br />
supply in these applications, it is strongly<br />
recommended that an isolation transformer be used to<br />
isolate the power supply from harmful voltage surges.<br />
Grounded ac Power-Distribution System with Master-Control Relay<br />
➀<br />
Incoming<br />
AC<br />
L1<br />
L2<br />
L3<br />
Disc.<br />
1FU Suppressor<br />
L1 ➁<br />
2FU<br />
L2<br />
To Motor<br />
Starters<br />
3FU<br />
L3<br />
H 1 H 4 ➃<br />
H 3 H 2<br />
Back-panel<br />
➂<br />
Step-down<br />
Transformer<br />
Ground Bus<br />
Enclosure<br />
Wall<br />
FUSE<br />
Multiple E-stop switches<br />
X 1 X 2<br />
Start<br />
Grounded Conductor<br />
CRM<br />
Equipment-<br />
Grounding<br />
Conductors<br />
Grounding-electrode<br />
Conductor to<br />
Grounding-electrode<br />
System<br />
CRM<br />
Suppressor 1<br />
The I/O circuits form a net<br />
inductive load switched by the<br />
CRM contacts. Therefore, a<br />
suppressor is needed<br />
across the line at the load<br />
side of the CRM contacts.<br />
CRM<br />
Input<br />
Sensor<br />
L1<br />
Input<br />
Module<br />
Wiring<br />
Arm<br />
Controller<br />
Power Supply<br />
➄<br />
Suppressor<br />
Output Module<br />
Wiring Arm<br />
GND<br />
N or L2<br />
Output<br />
Actuator<br />
CRM<br />
User DC<br />
Supply<br />
<br />
<br />
To DC I/O<br />
actuators/<br />
sensors<br />
Connect<br />
when applicable<br />
➀ To minimize EMI generation, connect a suppressor across an inductive load. For more information on selecting surge suppressors, see page 2–24.<br />
➁ Contact motor manufacturer for recommended surge supression for motors.<br />
➂ In applications where severe energy is re-generated by motors when power is removed, use an isolation/constant-voltage transformer in place of the step-down<br />
transformer.<br />
➃ In many applications, a second transformer provides power to the input circuits and power supplies for isolation from the output circuits.<br />
➄ Connect a suppressor here to minimize EMI generation from the net inductive load switched by the CRM contacts.<br />
suppressors, see page 2–24.<br />
For more information on selecting surge<br />
Publication <strong>1747</strong>-6.2