G–6 Communicating with Devices on an Ethernet Network<br />
The BOOTP request can be disabled by clearing the BOOTP Enable<br />
parameter in the channel Configuration File. When BOOTP Enable<br />
is cleared (disabled), the SLC 5/05 uses the existing channel<br />
configuration data.<br />
Important: If BOOTP is disabled, or no BOOTP server exists on<br />
the network, you must use SLC 500 programming<br />
software to enter/change the IP address for<br />
each processor. See page G–5 for that configuration<br />
procedure.<br />
The host system’s BOOTP configuration file must be updated to<br />
service requests from SLC 5/05 processors. The following<br />
parameters must be configured:<br />
Parameter<br />
IP Address<br />
Subnet Mask<br />
Gateway<br />
Note:<br />
Description<br />
A unique IP Address for the SLC 5/05 processor.<br />
Specifies the net and local subnet mask as per the standard on<br />
subnetting RFC 950, Internet Standard Subnetting Procedure.<br />
Specifies the IP address of a gateway on the same subnet as the<br />
SLC 5/05 that provides connections to another IP network.<br />
If you do not have BOOTP Server capabilities on your<br />
network, and you want to dynamically configure<br />
Channel 1, contact your local Allen-Bradley<br />
representative to obtain a free BOOTP Utility diskette.<br />
When BOOTP is enabled, the following events occur at power-up:<br />
• The processor broadcasts a BOOTP-request message containing its<br />
hardware address over the local network or subnet.<br />
• The BOOTP server compares the hardware address with the addresses<br />
in its look-up table in the BOOTPTAB file.<br />
• The BOOTP server sends a message back to the processor with the IP<br />
address and other network information that corresponds to the hardware<br />
address it received.<br />
With all hardware and IP addresses in one location, you can easily change<br />
IP addresses in the BOOTP configuration file if your network needs change.<br />
Using DOS/Windows BOOTP<br />
The optional BOOTP Server diskette contains DOS-based and<br />
Windows-based BOOTP server utilities. Both provide BOOTP<br />
services for SLC 5/05 processors. Regardless of the platform you are<br />
using, you must:<br />
• install the boot-server utility<br />
• edit the boot-server configuration file<br />
• run the boot-server utility<br />
Publication <strong>1747</strong>-6.2