Selecting Your Hardware Components<br />

2–25<br />

!<br />

ATTENTION: Damage could occur to SLC 500 triac<br />

outputs if you use suppressors having RC networks.<br />

Allen-Bradley AC surge suppressors not recommended<br />

for use with triacs include Catalog Numbers<br />

199-FSMA1, 199-FSMA2, 1401-N10, and 700-N24.<br />

Allen-Bradley surge suppressors recommended for use with<br />

Allen-Bradley relays, contactors, and starters are shown in the table<br />

below.<br />

Device<br />

Bulletin 509 Motor Starter<br />

Bulletin 509 Motor Starter<br />

120V ac<br />

240V ac<br />

Coil Voltage<br />

Suppressor Catalog<br />

Number<br />

599-K04 ➀<br />

599-KA04 ➀<br />

Bulletin 100 Contactor 120V ac<br />

199-FSMA1 ➁<br />

Bulletin 100 Contactor 240V ac<br />

199-F5MA2 ➁<br />

Bulletin 709 Motor Starter 120V ac 1401-N10 ➁<br />

Bulletin 700 Type R, RM<br />

Relays<br />

Bulletin 700 Type R Relay<br />

Bulletin 700 Type RM Relay<br />

Bulletin 700 Type R Relay<br />

Bulletin 700 Type RM Relay<br />

Bulletin 700 Type R Relay<br />

Bulletin 700 Type RM Relay<br />

Bulletin 700 Type R Relay<br />

Bulletin 700 Type RM Relay<br />

Bulletin 700 Type R Relay<br />

Bulletin 700 Type RM Relay<br />

Bulletin 700 Type N, P, or PK<br />

Relay<br />

Miscellaneous electromagnetic<br />

devices limited to 35 sealed<br />

VA<br />

AC coil<br />

12V dc<br />

12V dc<br />

24V dc<br />

24V dc<br />

48V dc<br />

48V dc<br />

115-125V dc<br />

115-125V dc<br />

230-250V dc<br />

230-250V dc<br />

150V max, AC or DC<br />

150V max, AC or DC<br />

None Required<br />

700-N22<br />

700-N28<br />

700-N10<br />

700-N13<br />

700-N16<br />

700-N17<br />

700-N11<br />

700-N14<br />

700-N12<br />

700-N15<br />

700-N24 ➁<br />

700-N24 ➁<br />

➀ Series C or later of these catalog numbers do not contain capacitors. They are recommended for<br />

use with SLC 500 triac outputs.<br />

➁ Not recommended for use with triac outputs.<br />