System Installation Recommendations<br />
3–3<br />
Preventing Excessive Heat<br />
For most applications, normal convection cooling will keep the<br />
adapter components within the specified operating range of 0° C to<br />
+60° C (+32° F to +140° F). Proper spacing of components within<br />
the enclosure is usually sufficient for heat dissipation.<br />
In some applications, a substantial amount of heat is produced by<br />
other equipment inside or outside the enclosure. In this case, place<br />
blower fans inside the enclosure to assist in air circulation and to<br />
reduce “hot spots” near the adapter.<br />
Additional cooling provisions might be necessary when high ambient<br />
temperatures are encountered.<br />
Important:<br />
Do not bring in unfiltered outside air. It may introduce<br />
harmful contaminants of dirt that could cause improper<br />
operation or damage to components. In extreme cases,<br />
you may need to use air conditioning to protect against<br />
heat build-up within the enclosure.<br />
Grounding Guidelines<br />
In solid-state control systems, grounding helps limit the effects of<br />
electrical noise due to electromagnetic interference (EMI). The<br />
ground path for the adapter and its enclosure is provided by the<br />
equipment grounding conductor.<br />
Normal Electrical Noise Conditions<br />
Severe Electrical Noise Conditions<br />
5.2 mm2 (10 AWG)<br />
to Ground Bus<br />
Chassis Mounting Tab<br />
Size M4 or M5<br />
(#10 or #12)<br />
Internal Star<br />
Washer<br />
Chassis<br />
Mounting Tab<br />
Size M4 or M5<br />
(#10 or #12)<br />
Hardware<br />
Ground<br />
Lug<br />
Size M4 or M5<br />
(#10 or #12)<br />
Internal Star<br />
Washers<br />
Size M4 or M5<br />
(#10 or #12)<br />
Hardware<br />
Tapped Hole<br />
(Minimum of Three<br />
Threads)<br />
Tapped Hole<br />
(Minimum of<br />
Three Threads)<br />
Scrape paint off panel to insure<br />
electrical connection between<br />
chassis<br />
and grounded metal panel.<br />
Metal Panel<br />
(Must be connected to<br />
earth ground.)<br />
Scrape paint off panel to insure<br />
electrical connection between chassis<br />
and grounded metal panel.<br />
Metal Panel<br />
(Must be connected to<br />
earth ground.)<br />
Publication <strong>1747</strong>-6.2