System Installation Recommendations<br />

3–3<br />

Preventing Excessive Heat<br />

For most applications, normal convection cooling will keep the<br />

adapter components within the specified operating range of 0° C to<br />

+60° C (+32° F to +140° F). Proper spacing of components within<br />

the enclosure is usually sufficient for heat dissipation.<br />

In some applications, a substantial amount of heat is produced by<br />

other equipment inside or outside the enclosure. In this case, place<br />

blower fans inside the enclosure to assist in air circulation and to<br />

reduce “hot spots” near the adapter.<br />

Additional cooling provisions might be necessary when high ambient<br />

temperatures are encountered.<br />

Important:<br />

Do not bring in unfiltered outside air. It may introduce<br />

harmful contaminants of dirt that could cause improper<br />

operation or damage to components. In extreme cases,<br />

you may need to use air conditioning to protect against<br />

heat build-up within the enclosure.<br />

Grounding Guidelines<br />

In solid-state control systems, grounding helps limit the effects of<br />

electrical noise due to electromagnetic interference (EMI). The<br />

ground path for the adapter and its enclosure is provided by the<br />

equipment grounding conductor.<br />

Normal Electrical Noise Conditions<br />

Severe Electrical Noise Conditions<br />

5.2 mm2 (10 AWG)<br />

to Ground Bus<br />

Chassis Mounting Tab<br />

Size M4 or M5<br />

(#10 or #12)<br />

Internal Star<br />

Washer<br />

Chassis<br />

Mounting Tab<br />

Size M4 or M5<br />

(#10 or #12)<br />

Hardware<br />

Ground<br />

Lug<br />

Size M4 or M5<br />

(#10 or #12)<br />

Internal Star<br />

Washers<br />

Size M4 or M5<br />

(#10 or #12)<br />

Hardware<br />

Tapped Hole<br />

(Minimum of Three<br />

Threads)<br />

Tapped Hole<br />

(Minimum of<br />

Three Threads)<br />

Scrape paint off panel to insure<br />

electrical connection between<br />

chassis<br />

and grounded metal panel.<br />

Metal Panel<br />

(Must be connected to<br />

earth ground.)<br />

Scrape paint off panel to insure<br />

electrical connection between chassis<br />

and grounded metal panel.<br />

Metal Panel<br />

(Must be connected to<br />

earth ground.)<br />