Communicating with Devices on an Ethernet Network<br />

G–13<br />

Using BOOTP to Configure Channel 1 for <strong>Processor</strong>s on Subnets<br />

Configure the BOOTPTAB file according to the subnet mask and<br />

gateway address for each SLC 5/05 processor on the link. See the<br />

example below and the corresponding BOOTPTAB file on the<br />

next page.<br />

Important: Because BOOTP requests are seen only on the local<br />

subnet, each subnet needs its own BOOTP server and<br />

BOOTPTAB file.<br />

personal computer WINDOWS<br />

or HP 9000 or VAX computer<br />

BOOTP<br />

server<br />

Subnet A<br />

SLC 5/05<br />

processor<br />

Ethernet TCP/IP network<br />

130.151.194.xxx<br />

Hostname: Iota1<br />

IP address: 130.151.194.19<br />

Subnet Mask: 255.255.255.0<br />

Gateway Address: 130.151.194.1<br />

130.151.194.1<br />

Ethernet gateway<br />

or “router”<br />

BOOTP<br />

server<br />

130.151.132.1 130.151.138.1<br />

BOOTP<br />

server<br />

130.151.132.xxx<br />

130.151.138.xxx<br />

Subnet B<br />

SLC 5/05<br />

processor<br />

SLC 5/05<br />

processor<br />

Subnet C<br />

Hostname: Iota2<br />

IP address: 130.151.132.110<br />

Subnet Mask: 255.255.255.0<br />

Gateway<br />

Address: 130.151.132.1<br />

Hostname: Iota3<br />

IP address: 130.151.138.123<br />

Subnet Mask: 255.255.255.0<br />

Gateway<br />

Address: 130.151.138.1<br />

Publication <strong>1747</strong>-6.2