Configuration<br />
July 2012<br />
Section 3 Configuration<br />
Guided Setup<br />
Field Communicator Configure > Guided Setup (2‐1)<br />
To quickly setup the instrument, the following procedures will guide you through the process.<br />
Device Setup—This procedure is used to configure actuator and valve information, calibrate the valve assembly, and<br />
assign the tuning set for the valve assembly.<br />
Performance Tuner (instrument level AD, PD, ODV)—This procedure executes a simple step response test and then<br />
calculates a recommended set of gain values based on the response of the control valve. See page 26 for additional<br />
information.<br />
Stabilize Optimize (instrument level HC)—This procedure permits you to adjust valve response by changing the<br />
digital valve controller tuning. See page 26 for additional information.<br />
Manual Setup33<br />
Manual Setup allows you to configure the digital valve controller to your application. Table 3‐1 lists the default settings<br />
for a standard factory configuration. You can adjust actuator response, set the various modes, alerts, ranges, travel<br />
cutoffs and limits. You can also restart the instrument and set the protection.<br />
Table 3‐1. Default Detailed Setup Parameters<br />
Instrument<br />
Configuration<br />
Dynamic Response and<br />
Tuning<br />
Setup Parameter Default Setting (1)<br />
Control Mode<br />
Analog<br />
Restart Control Mode<br />
Resume Last<br />
Analog In Range Low<br />
4 mA<br />
Analog In Range High<br />
20 mA<br />
Analog Input Units<br />
mA<br />
Local AutoCal Button<br />
Disabled<br />
Polling Address 0<br />
Burst Mode Enable<br />
No<br />
Burst Command 3<br />
Cmd 3 (Trending) Pressure<br />
A-B<br />
Input Characterization<br />
Linear<br />
Travel Limit High 125%<br />
Travel Limit Low -25%<br />
Travel/Pressure Cutoff High 99.46%<br />
Travel/Pressure Cutoff Low 0.50%<br />
Set Point Rate Open<br />
0%/sec<br />
Set Point Rate Close<br />
0%/sec<br />
Set Point Filter Time (Lag Time)<br />
0 sec<br />
Integrator Enable<br />
Yes<br />
Integral Gain<br />
9.4 repeats/minute<br />
Integral Deadzone 0.26%<br />
-continued on next page-<br />
15