Section 3 Configuration<br />

Guided Setup<br />

Field Communicator Configure > Guided Setup (2‐1)<br />

To quickly setup the instrument, the following procedures will guide you through the process.<br />

Device Setup—This procedure is used to configure actuator and valve information, calibrate the valve assembly, and<br />

assign the tuning set for the valve assembly.<br />

Performance Tuner (instrument level AD, PD, ODV)—This procedure executes a simple step response test and then<br />

calculates a recommended set of gain values based on the response of the control valve. See page 26 for additional<br />

information.<br />

Stabilize Optimize (instrument level HC)—This procedure permits you to adjust valve response by changing the<br />

digital valve controller tuning. See page 26 for additional information.<br />

Manual Setup33<br />

Manual Setup allows you to configure the digital valve controller to your application. Table 3‐1 lists the default settings<br />

for a standard factory configuration. You can adjust actuator response, set the various modes, alerts, ranges, travel<br />

cutoffs and limits. You can also restart the instrument and set the protection.<br />

Table 3‐1. Default Detailed Setup Parameters<br />

Instrument<br />

Configuration<br />

Dynamic Response and<br />

Tuning<br />

Setup Parameter Default Setting (1)<br />

Control Mode<br />

Analog<br />

Restart Control Mode<br />

Resume Last<br />

Analog In Range Low<br />

4 mA<br />

Analog In Range High<br />

20 mA<br />

Analog Input Units<br />

mA<br />

Local AutoCal Button<br />

Disabled<br />

Polling Address 0<br />

Burst Mode Enable<br />

No<br />

Burst Command 3<br />

Cmd 3 (Trending) Pressure<br />

A-B<br />

Input Characterization<br />

Linear<br />

Travel Limit High 125%<br />

Travel Limit Low -25%<br />

Travel/Pressure Cutoff High 99.46%<br />

Travel/Pressure Cutoff Low 0.50%<br />

Set Point Rate Open<br />

0%/sec<br />

Set Point Rate Close<br />

0%/sec<br />

Set Point Filter Time (Lag Time)<br />

0 sec<br />

Integrator Enable<br />

Yes<br />

Integral Gain<br />

9.4 repeats/minute<br />

Integral Deadzone 0.26%<br />

-continued on next page-<br />

15