Instruction Manual<br />

D103605X012<br />

Maintenance and Troubleshooting<br />

July 2012<br />

3. Separate the module base from the housing by performing the Removing the Module Base procedure.<br />

4. Disconnect the terminal box wiring connector from the PWB assembly (key 50).<br />

5. Remove the screw (key 72). Pull the terminal box assembly straight out of the housing.<br />

Replacing the Terminal Box<br />

Note<br />

Inspect all O‐rings for wear and replace as necessary.<br />

1. Apply lubricant, silicone sealant to the O‐ring (key 34) and install the O‐ring over the stem of the terminal box.<br />

2. Insert the terminal box assembly stem into the housing until it bottoms out. Position the terminal box assembly so<br />

that the hole for the screw (key 72) in the terminal box aligns with the threaded hole in the housing. Install the<br />

screw (key 72).<br />

3. Connect the terminal box wiring connector to the PWB assembly (key 50). Orientation of the connector is required.<br />

4. Reassemble the module base to the housing by performing the Replacing the Module Base procedure.<br />

5. Reconnect the field wiring as noted in step 2 in the Removing the Terminal Box procedure.<br />

6. Apply lubricant, silicone sealant to the O‐ring (key 36) and install the O‐ring over the 2‐5/8 inch threads of the<br />

terminal box. Use of a tool is recommended to prevent cutting the O‐ring while installing it over the threads.<br />

7. Apply lithium grease (key 63) to the 2‐5/8 inch threads on the terminal box to prevent seizing or galling when the<br />

cap is installed.<br />

8. Screw the cap (key 4) onto the terminal box.<br />

9. Install a set screw (key 58) into the cap (key 4). Loosen the cap (not more than 1 turn) to align the set screw over<br />

one of the recesses in the terminal box. Tighten the set screw (key 58).<br />

DVC6215 Feedback Unit<br />

There are no replaceable parts on the DVC6215 feedback unit. Contact your Emerson Process Management if a<br />

replacement DVC6215 feedback unit is needed.<br />

Troubleshooting<br />

If communication or output difficulties are experienced with the instrument, refer to the troubleshooting chart in<br />

table 6‐3. Also see the <strong>DVC6200</strong> Technical Support Checklist on page 68.<br />