Configuration<br />

July 2012<br />

Table 3‐7. Values for Disabling Partial Stroke Pressure Limit<br />

Actuator Type Relay Type Zero Power Condition Partial Stroke Start Point Partial Stroke Pressure Limit (Disabled)<br />

Open 0.0<br />

Closed<br />

Closed<br />

Psupply<br />

A or C<br />

Open<br />

Psupply<br />

Open<br />

Closed 0.0<br />

Single Acting<br />

Open<br />

Psupply<br />

Closed<br />

Closed 0.0<br />

B<br />

Open 0.0<br />

Open<br />

Closed<br />

Psupply<br />

Double Acting<br />

A<br />

Closed<br />

Open<br />

Open<br />

Closed<br />

Open<br />

Closed<br />

-Psupply<br />

Psupply<br />

Psupply<br />

-Psupply<br />

3. Run a partial stroke test.<br />

4. Select the Press/Time radio button on the partial stroke graph (refer to the example in figure 3‐4, bottom plot). If<br />

the actuator pressure starts high and moves low, find the minimum actuator pressure (Pmin). If the actuator<br />

pressure starts low and moves high, find the maximum actuator pressure (Pmax). Double­acting actuators will<br />

display differential pressure. Use table 3‐8 to estimate the partial stroke pressure limit.<br />

Table 3‐8. Estimates for Partial Stroke Pressure Limits<br />

Actuator Style Relay Type Zero Power Condition PST Starting Point Partial Stroke Pressure Limit (1)<br />

Open<br />

Pmin - 0.25 * (Bench Set High - Bench Set Low)<br />

Closed<br />

Closed<br />

Pmax + 0.25 * (Bench Set High - Bench Set Low)<br />

A or C<br />

Open<br />

Pmax + 0.25 * (Bench Set High - Bench Set Low)<br />

Open<br />

Spring and<br />

Closed<br />

Pmin - 0.25 * (Bench Set High - Bench Set Low)<br />

Diaphragm<br />

Open<br />

Pmax + 0.25 * (Bench Set High - Bench Set Low)<br />

Closed<br />

Closed<br />

Pmin - 0.25 * (Bench Set High - Bench Set Low)<br />

B<br />

Open<br />

Pmin - 0.25 * (Bench Set High - Bench Set Low)<br />

Open<br />

Closed<br />

Pmax + 0.25 * (Bench Set High - Bench Set Low)<br />

Single Acting Piston<br />

A or C<br />

B<br />

Closed<br />

Open<br />

Closed<br />

Open<br />

Open<br />

Closed<br />

Open<br />

Closed<br />

Open<br />

Closed<br />

Open<br />

Closed<br />

0.5 * Pmin<br />

Pmax + 0.5 * (Psupply - Pmax)<br />

Pmax + 0.5 * (Psupply - Pmax)<br />

0.5 * Pmin<br />

Pmax + 0.5 * (Psupply - Pmax)<br />

0.5 * Pmin<br />

0.5 * Pmin<br />

Pmax + 0.5 * (Psupply - Pmax)<br />

Double Acting Piston<br />

A<br />

Closed<br />

Open<br />

Open<br />

Closed<br />

Open<br />

Closed<br />

Pmin - 0.5 * (Psupply + Pmin)<br />

Pmax + 0.5 * (Psupply - Pmax)<br />

Pmax + 0.5 * (Psupply - Pmax)<br />

Pmin - 0.5 * (Psupply + Pmin)<br />

5. Enable the parameters that were previously disabled:<br />

Travel Deviation Alert - set to 1.5x the maximum travel deviation between travel set point and travel.<br />

End Point Pressure Control - enable<br />

Partial Stroke Pressure Limit - calculate the value using table 3‐8.<br />

31