Table 3‐7. Values for Disabling Partial Stroke Pressure Limit<br />
Actuator Type Relay Type Zero Power Condition Partial Stroke Start Point Partial Stroke Pressure Limit (Disabled)<br />
Open 0.0<br />
Closed<br />
Closed<br />
Psupply<br />
A or C<br />
Open<br />
Psupply<br />
Open<br />
Closed 0.0<br />
Single Acting<br />
Open<br />
Psupply<br />
Closed<br />
Closed 0.0<br />
B<br />
Open 0.0<br />
Open<br />
Closed<br />
Psupply<br />
Double Acting<br />
A<br />
Closed<br />
Open<br />
Open<br />
Closed<br />
Open<br />
Closed<br />
-Psupply<br />
Psupply<br />
Psupply<br />
-Psupply<br />
3. Run a partial stroke test.<br />
4. Select the Press/Time radio button on the partial stroke graph (refer to the example in figure 3‐4, bottom plot). If<br />
the actuator pressure starts high and moves low, find the minimum actuator pressure (Pmin). If the actuator<br />
pressure starts low and moves high, find the maximum actuator pressure (Pmax). Doubleacting actuators will<br />
display differential pressure. Use table 3‐8 to estimate the partial stroke pressure limit.<br />
Table 3‐8. Estimates for Partial Stroke Pressure Limits<br />
Actuator Style Relay Type Zero Power Condition PST Starting Point Partial Stroke Pressure Limit (1)<br />
Open<br />
Pmin - 0.25 * (Bench Set High - Bench Set Low)<br />
Closed<br />
Closed<br />
Pmax + 0.25 * (Bench Set High - Bench Set Low)<br />
A or C<br />
Open<br />
Pmax + 0.25 * (Bench Set High - Bench Set Low)<br />
Open<br />
Spring and<br />
Closed<br />
Pmin - 0.25 * (Bench Set High - Bench Set Low)<br />
Diaphragm<br />
Open<br />
Pmax + 0.25 * (Bench Set High - Bench Set Low)<br />
Closed<br />
Closed<br />
Pmin - 0.25 * (Bench Set High - Bench Set Low)<br />
B<br />
Open<br />
Pmin - 0.25 * (Bench Set High - Bench Set Low)<br />
Open<br />
Closed<br />
Pmax + 0.25 * (Bench Set High - Bench Set Low)<br />
Single Acting Piston<br />
A or C<br />
B<br />
Closed<br />
Open<br />
Closed<br />
Open<br />
Open<br />
Closed<br />
Open<br />
Closed<br />
Open<br />
Closed<br />
Open<br />
Closed<br />
0.5 * Pmin<br />
Pmax + 0.5 * (Psupply - Pmax)<br />
Pmax + 0.5 * (Psupply - Pmax)<br />
0.5 * Pmin<br />
Pmax + 0.5 * (Psupply - Pmax)<br />
0.5 * Pmin<br />
0.5 * Pmin<br />
Pmax + 0.5 * (Psupply - Pmax)<br />
Double Acting Piston<br />
A<br />
Closed<br />
Open<br />
Open<br />
Closed<br />
Open<br />
Closed<br />
Pmin - 0.5 * (Psupply + Pmin)<br />
Pmax + 0.5 * (Psupply - Pmax)<br />
Pmax + 0.5 * (Psupply - Pmax)<br />
Pmin - 0.5 * (Psupply + Pmin)<br />
5. Enable the parameters that were previously disabled:<br />
Travel Deviation Alert - set to 1.5x the maximum travel deviation between travel set point and travel.<br />
End Point Pressure Control - enable<br />
Partial Stroke Pressure Limit - calculate the value using table 3‐8.<br />