26.12.2014 Views

Fisher® FIELDVUE DVC6200 Digital Valve Controller

Fisher® FIELDVUE DVC6200 Digital Valve Controller

Fisher® FIELDVUE DVC6200 Digital Valve Controller

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Instruction Manual<br />

D103605X012<br />

Configuration<br />

July 2012<br />

Description—Enter a description for the application with up to 16 characters. The description provides a longer<br />

user‐defined electronic label to assist with more specific instrument identification than is available with the HART<br />

tag.<br />

Message—Enter any message with up to 32 characters. Message provides the most specific user‐defined means for<br />

identifying individual instruments in multi‐instrument environments.<br />

Polling Address—If the digital valve controller is used in point‐to‐point operation, the Polling Address is 0. When<br />

several devices are connected in the same loop, such as for split ranging, each device must be assigned a unique<br />

polling address. The Polling Address is set to a value between 0 and 63 for HART 7 and 0 and 15 for HART 5. To<br />

change the polling address the instrument must be Out Of Service.<br />

For the Field Communicator to be able to communicate with a device whose polling address is not 0, it must be<br />

configured to automatically search for all or specific connected devices.<br />

Serial Numbers<br />

Instrument Serial Number—Enter the serial number on the instrument nameplate, up to 12 characters.<br />

<strong>Valve</strong> Serial Number—Enter the serial number for the valve in the application, up to 12 characters.<br />

Units<br />

Pressure Units—Defines the output and supply pressure units in either psi, bar, kPa, or kg/cm 2 .<br />

Temperature Units—Degrees Fahrenheit or Celsius. The temperature measured is from a sensor mounted on the<br />

digital valve controller's printed wiring board.<br />

Analog Input Units—Permits defining the Analog Input Units in mA or percent of 4-20 mA range.<br />

Terminal Box<br />

Calibration (CAL) Button—This button is near the wiring terminals in the terminal box and provides a quick means to<br />

autocalibrate the instrument. The button must be pressed for 3 to 10 seconds. Autocalibration will move the valve<br />

through the full range of travel whether the Instrument Mode is In Service or Out of Service. However, if the Write<br />

Protection is Protected, this button will not be active. To abort, press the button again for 1 second. The calibration<br />

button is disabled by default.<br />

Auxiliary Terminal Action—These wire terminals can be configured to initiate a partial stroke test upon detection of<br />

a short across the (+) and (-) terminals. The terminals must be shorted for 3 to 10 seconds.<br />

Note<br />

Auxiliary Terminal Action is only available for instrument level ODV.<br />

Analog Input Range<br />

Input Range Hi—Permits setting the Input Range High value. Input Range High should correspond to Travel Range<br />

High, if the Zero Power Condition is configured as closed. If the Zero Power Condition is configured as open, Input<br />

Range High corresponds to Travel Range Low. See figure 3‐1.<br />

17

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!