Instruction Manual<br />
D103605X012<br />
Device Information, Diagnostics, and Alerts<br />
July 2012<br />
Travel History<br />
Cycle Count High Alert—This alert is active if the Cycle Counter exceeds the Cycle Count Alert Point. The Cycle Count<br />
records the number of times the travel changes direction when it is outside of the deadband. To clear the alert, set<br />
the Cycle Counter to a value less than the alert point.<br />
Travel Accumulator High Alert—This alert is active if the Travel Accumulator exceeds the Travel Accumulator Alert<br />
Point. The Travel Accumulator totalizes the travel of the valve when the deadband is exceeded. To clear the alert,<br />
set the Travel Accumulator to a value less than the alert point.<br />
Note<br />
The Cycle Count / Travel Accumulator Deadband applies to both the Cycle Count High Alert and the Travel Accumulator High<br />
Alert.<br />
The deadband is the percent (%) of ranged travel around a travel reference point. The travel reference point gets<br />
reestablished to the point of travel reversal that occurs outside of the deadband. The deadband must be exceeded<br />
before a change in travel direction will be counted as a cycle and the accumulated travel (up to the point of travel<br />
reversal) is added to the total accumulation. See figure 5‐2.<br />
Figure 5‐2. Cycle Counter and Travel Accumulator Deadband Example (set at 10%)<br />
DEADBAND EXCEEDED, NEW<br />
REFERENCE POINT ESTABLISHED<br />
DEADBAND<br />
REFERENCE POINT<br />
DEADBAND (+/- 5%)<br />
VALVE POSITION<br />
TIME<br />
DEADBAND<br />
DARK SEGMENTS REPRESENT THE AMOUNT OF TRAVEL<br />
THAT WILL BE ADDED TO THE TRAVEL ACCUMULATOR<br />
E1473<br />
CYCLE COUNTER INCREMENTS<br />
Alert Record<br />
Alert Record Not Empty Alert—This alert is active when there are 1 or more alerts stored in the alert record.<br />
Alert Record Full Alert—This alert is active when the alert record is full. Additional alerts that are detected will not be<br />
saved to the alert record until the alert record is cleared.<br />
51