Instruction Manual<br />

D103605X012<br />

Calibration<br />

July 2012<br />

PST Calibration (ODV Instrument Level only)<br />

This procedure permits you to run the Partial Stroke Calibration, which enables the Partial Stroke Test. It establishes<br />

values for Partial Stroke Pressure Limit, Pressure Set Point and Pressure Saturation Time for End Point Pressure Control,<br />

Travel Deviation Alert Point and Travel Deviation Time. The Partial Stroke Calibration also sets default values for max<br />

travel movement, test speed, and test pause time.<br />

Note<br />

You must take the instrument out of service before running Partial Stroke Calibration.<br />

Ensure that the instrument is put back in service after the completing the calibration procedure.<br />