Fisher® FIELDVUE DVC6200 Digital Valve Controller
Fisher® FIELDVUE DVC6200 Digital Valve Controller
Fisher® FIELDVUE DVC6200 Digital Valve Controller
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Instruction Manual<br />
D103605X012<br />
Configuration<br />
July 2012<br />
Alert Setup<br />
Field Communicator Configure > Alert Setup (2‐3)<br />
An alert is a notification that the instrument has detected a problem. A shutdown is an action that the instrument<br />
takes to drive the air output to the Zero Power Condition as per figure 3‐3. Some alerts can be configured to shutdown<br />
the instrument. Refer to table 3‐9 for default alert and shutdown settings.<br />
Alerts may be enabled or disabled with the instrument In Service, Out of Service, Protected, or Not Protected.<br />
However, the instrument must be Not Protected to enable or disable a shutdown. Alerts are not processed when a<br />
diagnostic is in progress.<br />
If shutdown is enabled, and the alert is active, the instrument will latch in the shutdown state until power to the<br />
instrument is cycled and the alert has cleared. While in the shutdown condition, HART communication will continue if<br />
the instrument remains powered.<br />
For a detailed explanation of the alerts and the recommended actions, refer to Section 5.<br />
Table 3‐9. Default Alert and Shutdown Settings<br />
ALERT DEFAULT ALERT SETTING DEFAULT SHUTDOWN SETTING<br />
Travel Sensor Failure Enabled Disabled<br />
Temperature Sensor Failure Enabled Disabled<br />
Minor Loop Sensor Failure Enabled Disabled<br />
Pressure Sensor Failure Enabled Disabled<br />
Drive Current Failure Enabled Disabled<br />
Critical NVM Failure Enabled Disabled<br />
Non-Critical NVM Failure Enabled Disabled<br />
Flash Integrity Failure Enabled Disabled<br />
Reference Voltage Failure Enabled Disabled<br />
Drive Signal Out of Range Enabled Not Available<br />
Supply Pressure Low () Enabled Not Available<br />
Travel Deviation Enabled Not Available<br />
Pressure Fallback Active () Enabled Not Available<br />
High Travel Disabled Not Available<br />
Low Travel Disabled Not Available<br />
High-High Travel Disabled Not Available<br />
Low-Low Travel Disabled Not Available<br />
Travel Limit/Cutoff High Disabled Not Available<br />
Travel Limit/Cutoff Low Disabled Not Available<br />
Integrator Saturated High Disabled Not Available<br />
Integrator Saturated Low Disabled Not Available<br />
Cycle Count High Disabled Not Available<br />
Travel Accumulator High Disabled Not Available<br />
Output Circuit Communication Failure Disabled Not Available<br />
Alert Record Not Empty Disabled Not Available<br />
Alert Record Full Disabled Not Available<br />
Instrument Time is Approximate Disabled Not Available<br />
1. Instrument level AD, PD, or ODV only.<br />
35