Instruction Manual<br />

D103605X012<br />

Configuration<br />

July 2012<br />

Alert Setup<br />

Field Communicator Configure > Alert Setup (2‐3)<br />

An alert is a notification that the instrument has detected a problem. A shutdown is an action that the instrument<br />

takes to drive the air output to the Zero Power Condition as per figure 3‐3. Some alerts can be configured to shutdown<br />

the instrument. Refer to table 3‐9 for default alert and shutdown settings.<br />

Alerts may be enabled or disabled with the instrument In Service, Out of Service, Protected, or Not Protected.<br />

However, the instrument must be Not Protected to enable or disable a shutdown. Alerts are not processed when a<br />

diagnostic is in progress.<br />

If shutdown is enabled, and the alert is active, the instrument will latch in the shutdown state until power to the<br />

instrument is cycled and the alert has cleared. While in the shutdown condition, HART communication will continue if<br />

the instrument remains powered.<br />

For a detailed explanation of the alerts and the recommended actions, refer to Section 5.<br />

Table 3‐9. Default Alert and Shutdown Settings<br />

ALERT DEFAULT ALERT SETTING DEFAULT SHUTDOWN SETTING<br />

Travel Sensor Failure Enabled Disabled<br />

Temperature Sensor Failure Enabled Disabled<br />

Minor Loop Sensor Failure Enabled Disabled<br />

Pressure Sensor Failure Enabled Disabled<br />

Drive Current Failure Enabled Disabled<br />

Critical NVM Failure Enabled Disabled<br />

Non-Critical NVM Failure Enabled Disabled<br />

Flash Integrity Failure Enabled Disabled<br />

Reference Voltage Failure Enabled Disabled<br />

Drive Signal Out of Range Enabled Not Available<br />

Supply Pressure Low () Enabled Not Available<br />

Travel Deviation Enabled Not Available<br />

Pressure Fallback Active () Enabled Not Available<br />

High Travel Disabled Not Available<br />

Low Travel Disabled Not Available<br />

High-High Travel Disabled Not Available<br />

Low-Low Travel Disabled Not Available<br />

Travel Limit/Cutoff High Disabled Not Available<br />

Travel Limit/Cutoff Low Disabled Not Available<br />

Integrator Saturated High Disabled Not Available<br />

Integrator Saturated Low Disabled Not Available<br />

Cycle Count High Disabled Not Available<br />

Travel Accumulator High Disabled Not Available<br />

Output Circuit Communication Failure Disabled Not Available<br />

Alert Record Not Empty Disabled Not Available<br />

Alert Record Full Disabled Not Available<br />

Instrument Time is Approximate Disabled Not Available<br />

1. Instrument level AD, PD, or ODV only.<br />

35