Fisher® FIELDVUE DVC6200 Digital Valve Controller
Fisher® FIELDVUE DVC6200 Digital Valve Controller
Fisher® FIELDVUE DVC6200 Digital Valve Controller
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Instruction Manual<br />
D103605X012<br />
Configuration<br />
July 2012<br />
Outputs<br />
Field Communicator<br />
Configure > Manual Setup > Outputs (2-2-6) HC, AD, PD or (2-2-7) ODV<br />
Output Terminal Configuration<br />
Note<br />
These menu items are only available on units that have the optional 420 mA position transmitter or switch hardware installed.<br />
Output Terminal Enable—If using the optional output terminal for a Position Transmitter or Switch output, this must<br />
be Enabled.<br />
Function—The output terminals can be configured as one of the following:<br />
Transmitter - 420mA output that represents 0100% of the calibrated valve travel.<br />
Limit Switch - Discrete switch (1A max) that trips at a configurable point within 0100% of calibrated valve travel.<br />
Alert Switch - Discrete switch (1A max) that trips based on a configurable device alert.<br />
Fail Signal—Should the output circuit fail to operate properly, the output will attempt to drive to a known state.<br />
Depending on the nature of the failure, the circuit may or may not be able to achieve this fail state. When<br />
configured as a transmitter, the output can be configured to drive high (22.5 mA) or low (3.6 mA). When<br />
configured as a switch, the output can be configured to drive Closed or Open.<br />
Note<br />
On loss of positioner power, the switch circuit will always go to the open state. However, on loss of positioner power, the<br />
transmitter output will continue to operate as long as the transmitter circuit is still powered and functioning.<br />
Switch Configuration<br />
Note<br />
Switch Configuration is only available on units that have the optional 420 mA position transmitter or switch hardware installed.<br />
Limit Switch Trip Point—When the function is configured as a Limit Switch, this defines the threshold for the limit<br />
switch in percent of calibrated travel.<br />
Alert Switch Source—When the function is configured as a Alert Switch, this determines which alert will activate the<br />
switch. The alert choices are: Travel Deviation or Pressure Fallback.<br />
Switch Closed—This configures the action of the switch. The choices are: Below Trip Point / Alert Not Active or<br />
Above Trip Point / Alert Active.<br />
33