26.12.2014 Views

Fisher® FIELDVUE DVC6200 Digital Valve Controller

Fisher® FIELDVUE DVC6200 Digital Valve Controller

Fisher® FIELDVUE DVC6200 Digital Valve Controller

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Instruction Manual<br />

D103605X012<br />

Configuration<br />

July 2012<br />

Outputs<br />

Field Communicator<br />

Configure > Manual Setup > Outputs (2-2-6) HC, AD, PD or (2-2-7) ODV<br />

Output Terminal Configuration<br />

Note<br />

These menu items are only available on units that have the optional 4­20 mA position transmitter or switch hardware installed.<br />

Output Terminal Enable—If using the optional output terminal for a Position Transmitter or Switch output, this must<br />

be Enabled.<br />

Function—The output terminals can be configured as one of the following:<br />

Transmitter - 4­20mA output that represents 0­100% of the calibrated valve travel.<br />

Limit Switch - Discrete switch (1A max) that trips at a configurable point within 0­100% of calibrated valve travel.<br />

Alert Switch - Discrete switch (1A max) that trips based on a configurable device alert.<br />

Fail Signal—Should the output circuit fail to operate properly, the output will attempt to drive to a known state.<br />

Depending on the nature of the failure, the circuit may or may not be able to achieve this fail state. When<br />

configured as a transmitter, the output can be configured to drive high (22.5 mA) or low (3.6 mA). When<br />

configured as a switch, the output can be configured to drive Closed or Open.<br />

Note<br />

On loss of positioner power, the switch circuit will always go to the open state. However, on loss of positioner power, the<br />

transmitter output will continue to operate as long as the transmitter circuit is still powered and functioning.<br />

Switch Configuration<br />

Note<br />

Switch Configuration is only available on units that have the optional 4­20 mA position transmitter or switch hardware installed.<br />

Limit Switch Trip Point—When the function is configured as a Limit Switch, this defines the threshold for the limit<br />

switch in percent of calibrated travel.<br />

Alert Switch Source—When the function is configured as a Alert Switch, this determines which alert will activate the<br />

switch. The alert choices are: Travel Deviation or Pressure Fallback.<br />

Switch Closed—This configures the action of the switch. The choices are: Below Trip Point / Alert Not Active or<br />

Above Trip Point / Alert Active.<br />

33

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!