Fisher® FIELDVUE DVC6200 Digital Valve Controller
Fisher® FIELDVUE DVC6200 Digital Valve Controller
Fisher® FIELDVUE DVC6200 Digital Valve Controller
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Instruction Manual<br />
D103605X012<br />
Device Information, Diagnostics, and Alerts<br />
July 2012<br />
Variable Out of Range—This alert is active if there is a problem with one or more of the following: the analog input<br />
signal, the I/P converter, the pneumatic relay, or the printed wiring board.<br />
Field Device Malfunction—This alert is active if the pressure, position, or temperature sensors are providing invalid<br />
readings.<br />
Internal Sensor Out of Limits—This alert is active if there is a problem with either the pressure sensor or the printed<br />
wiring board assembly.<br />
Travel Sensor Alert—This alert is active if the sensed travel is outside the range of 25.0 to 125.0% of calibrated<br />
travel. If this alert is active, check the instrument mounting. Also, check that the electrical connection from the<br />
travel sensor is properly plugged into the printed wiring board assembly. After restarting the instrument, if the alert<br />
persists, troubleshoot the printed wiring board assembly or travel sensor.<br />
Temperature Sensor Alert—This alert is active when the instrument temperature sensor fails, or the sensor reading<br />
is outside of the range of 60 to 100°C (76 to 212°F). The temperature reading is used internally for temperature<br />
compensation of inputs. If this alert is active, restart the instrument. If the alert persists, replace the printed wiring<br />
board assembly.<br />
Pressure Sensor Alert—This alert is active if any of the 3 pressure sensor readings are outside the range of 24.0 to<br />
125.0% of the calibrated pressure for more than 60 seconds. If this alert is active, check the instrument supply<br />
pressure, ensure the printed wiring board assembly is properly mounted onto the module base assembly, and<br />
ensure the pressure sensor orings are properly installed. If the alert persists after restarting the instrument, replace<br />
the printed wiring board assembly.<br />
Minor Loop Sensor Alert—This alert is active if the pneumatic relay position reading is outside the valid range. If the<br />
alert persists, replace the printed wiring board.<br />
Loop Current Validation Alert—This alert is active if the loop current is significantly out of range, or if there is a<br />
problem with the analog circuit electronics. If this alert is active, restart the instrument with the loop current<br />
verified to be in the 420 mA range. If the alert persists, replace the printed wiring board.<br />
Note<br />
If the control system is known to output current beyond 25 mA, Shutdown on Loop Current Validation should not be enabled.<br />
Output Circuit Communication Failure—This alert is active if the output circuit is not responding. If configured as a<br />
position transmitter output, first make sure the transmitter circuit is powered. If the alert persists, make sure the<br />
DIP switch on the main electronics matches the configuration of the OUT terminals. If the alert is still active, replace<br />
the main electronics.<br />
Instrument Time is Approximate Alert—This alert is active if the instrument has been powered down since the last<br />
time the instrument clock was set. To clear the alert, reset the instrument time.<br />
Pressure<br />
Supply Pressure Alert—This alert is active if the supply pressure falls below the supply pressure alert point.<br />
Note<br />
The Supply Pressure Lo alert is available for instrument level AD, PD, and ODV.<br />
49