26.12.2014 Views

Fisher® FIELDVUE DVC6200 Digital Valve Controller

Fisher® FIELDVUE DVC6200 Digital Valve Controller

Fisher® FIELDVUE DVC6200 Digital Valve Controller

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Instruction Manual<br />

D103605X012<br />

Device Information, Diagnostics, and Alerts<br />

July 2012<br />

Variable Out of Range—This alert is active if there is a problem with one or more of the following: the analog input<br />

signal, the I/P converter, the pneumatic relay, or the printed wiring board.<br />

Field Device Malfunction—This alert is active if the pressure, position, or temperature sensors are providing invalid<br />

readings.<br />

Internal Sensor Out of Limits—This alert is active if there is a problem with either the pressure sensor or the printed<br />

wiring board assembly.<br />

Travel Sensor Alert—This alert is active if the sensed travel is outside the range of ­25.0 to 125.0% of calibrated<br />

travel. If this alert is active, check the instrument mounting. Also, check that the electrical connection from the<br />

travel sensor is properly plugged into the printed wiring board assembly. After restarting the instrument, if the alert<br />

persists, troubleshoot the printed wiring board assembly or travel sensor.<br />

Temperature Sensor Alert—This alert is active when the instrument temperature sensor fails, or the sensor reading<br />

is outside of the range of ­60 to 100°C (­76 to 212°F). The temperature reading is used internally for temperature<br />

compensation of inputs. If this alert is active, restart the instrument. If the alert persists, replace the printed wiring<br />

board assembly.<br />

Pressure Sensor Alert—This alert is active if any of the 3 pressure sensor readings are outside the range of ­24.0 to<br />

125.0% of the calibrated pressure for more than 60 seconds. If this alert is active, check the instrument supply<br />

pressure, ensure the printed wiring board assembly is properly mounted onto the module base assembly, and<br />

ensure the pressure sensor o­rings are properly installed. If the alert persists after restarting the instrument, replace<br />

the printed wiring board assembly.<br />

Minor Loop Sensor Alert—This alert is active if the pneumatic relay position reading is outside the valid range. If the<br />

alert persists, replace the printed wiring board.<br />

Loop Current Validation Alert—This alert is active if the loop current is significantly out of range, or if there is a<br />

problem with the analog circuit electronics. If this alert is active, restart the instrument with the loop current<br />

verified to be in the 4­20 mA range. If the alert persists, replace the printed wiring board.<br />

Note<br />

If the control system is known to output current beyond 25 mA, Shutdown on Loop Current Validation should not be enabled.<br />

Output Circuit Communication Failure—This alert is active if the output circuit is not responding. If configured as a<br />

position transmitter output, first make sure the transmitter circuit is powered. If the alert persists, make sure the<br />

DIP switch on the main electronics matches the configuration of the OUT terminals. If the alert is still active, replace<br />

the main electronics.<br />

Instrument Time is Approximate Alert—This alert is active if the instrument has been powered down since the last<br />

time the instrument clock was set. To clear the alert, reset the instrument time.<br />

Pressure<br />

Supply Pressure Alert—This alert is active if the supply pressure falls below the supply pressure alert point.<br />

Note<br />

The Supply Pressure Lo alert is available for instrument level AD, PD, and ODV.<br />

49

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!