Calibration<br />
July 2012<br />
Manual Calibration<br />
Two procedures are available to manually calibrate travel:<br />
Analog Adjust— This procedure is used when you can manually change the 4-20 mA current source to move the<br />
valve.<br />
<strong>Digital</strong> Adjust— This procedure is used when the 4-20 mA current source cannot be manually changed.<br />
Analog Calibration Adjust<br />
Connect a variable current source to the instrument LOOP + and LOOP - terminals. The current source should be<br />
capable of generating 4 to 20 mA.<br />
Follow the prompts on the Field Communicator display to calibrate the instrument's travel in percent.<br />
Note<br />
0% Travel = <strong>Valve</strong> Closed<br />
100% Travel = <strong>Valve</strong> Open<br />
1. Adjust the input current until the valve is near mid‐travel. Press OK.<br />
Note<br />
In steps 2 through 7 the accuracy of the current source adjustment affects the position accuracy.<br />
2. Adjust the current source until the valve is at 0% travel, then press OK.<br />
3. Adjust the current source until the valve is at 100% travel, then press OK.<br />
4. Adjust the current source until the valve is at 0% travel, then press OK.<br />
5. Adjust the current source until the valve is at 100% travel, then press OK.<br />
6. Adjust the current source until the valve is at 5% travel, then press OK.<br />
7. Adjust the current source until the valve is at 95% travel, then press OK.<br />
8. Place the instrument In Service and verify that the travel properly tracks the current source.<br />
<strong>Digital</strong> Calibration Adjust<br />
Connect a variable current source to the instrument LOOP + and LOOP - terminals. The current source should be set<br />
between 4 and 20 mA.<br />
Follow the prompts on the Field Communicator display to calibrate the instrument's travel in percent.<br />
1. Adjust the input current until the valve is near mid‐travel. Press OK.<br />
Note<br />
0% Travel = <strong>Valve</strong> Closed<br />
100% Travel = <strong>Valve</strong> Open<br />