Instruction Manual<br />

D103605X012<br />

Calibration<br />

July 2012<br />

Manual Calibration<br />

Two procedures are available to manually calibrate travel:<br />

Analog Adjust— This procedure is used when you can manually change the 4-20 mA current source to move the<br />

valve.<br />

<strong>Digital</strong> Adjust— This procedure is used when the 4-20 mA current source cannot be manually changed.<br />

Analog Calibration Adjust<br />

Connect a variable current source to the instrument LOOP + and LOOP - terminals. The current source should be<br />

capable of generating 4 to 20 mA.<br />

Follow the prompts on the Field Communicator display to calibrate the instrument's travel in percent.<br />

Note<br />

0% Travel = <strong>Valve</strong> Closed<br />

100% Travel = <strong>Valve</strong> Open<br />

1. Adjust the input current until the valve is near mid‐travel. Press OK.<br />

Note<br />

In steps 2 through 7 the accuracy of the current source adjustment affects the position accuracy.<br />

2. Adjust the current source until the valve is at 0% travel, then press OK.<br />

3. Adjust the current source until the valve is at 100% travel, then press OK.<br />

4. Adjust the current source until the valve is at 0% travel, then press OK.<br />

5. Adjust the current source until the valve is at 100% travel, then press OK.<br />

6. Adjust the current source until the valve is at 5% travel, then press OK.<br />

7. Adjust the current source until the valve is at 95% travel, then press OK.<br />

8. Place the instrument In Service and verify that the travel properly tracks the current source.<br />

<strong>Digital</strong> Calibration Adjust<br />

Connect a variable current source to the instrument LOOP + and LOOP - terminals. The current source should be set<br />

between 4 and 20 mA.<br />

Follow the prompts on the Field Communicator display to calibrate the instrument's travel in percent.<br />

1. Adjust the input current until the valve is near mid‐travel. Press OK.<br />

Note<br />

0% Travel = <strong>Valve</strong> Closed<br />

100% Travel = <strong>Valve</strong> Open<br />

39