26.12.2014 Views

Fisher® FIELDVUE DVC6200 Digital Valve Controller

Fisher® FIELDVUE DVC6200 Digital Valve Controller

Fisher® FIELDVUE DVC6200 Digital Valve Controller

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Instruction Manual<br />

D103605X012<br />

Calibration<br />

July 2012<br />

Press OK when you have read this message.<br />

3. The value of the Analog Input appears on the display. Press OK to display the adjustment menu.<br />

4. From the adjustment menu, select the direction and size of adjustment to the displayed value.<br />

Selecting large, medium, and small adjustments causes changes of approximately 0.4 mA, 0.04 mA, and 0.004 mA,<br />

respectively.<br />

If the displayed value does not match the current source, press OK, then repeat this step (step 4) to further adjust the<br />

displayed value. When the displayed value matches the current source, select Done and go to step 5.<br />

5. Set the current source to the target value shown on the display. The target value is the Input Range High value.<br />

Press OK.<br />

6. The following message appears:<br />

Use the Increase and Decrease<br />

selections until the displayed<br />

current matches the target.<br />

Press OK when you have read this message.<br />

7. The value of the Analog Input appears on the display. Press OK to display the adjustment menu.<br />

8. From the adjustment menu, select the direction and size of adjustment to the displayed value. If the displayed value<br />

does not match the current source, press OK, then repeat this step (step 8) to further adjust the displayed value.<br />

When the displayed value matches the current source, select Done and go to step 9.<br />

9. Place the instrument In Service and verify that the analog input displayed matches the current source.<br />

Relay Adjustment<br />

Before beginning travel calibration, check the relay adjustment. Replace the digital valve controller cover when<br />

finished.<br />

Note<br />

Relay B and C are not user‐adjustable.<br />

Double‐Acting Relay<br />

The double‐acting relay is designated by “Relay A” on a label affixed to the relay itself. For double‐acting actuators, the<br />

valve must be near mid‐travel to properly adjust the relay. The Field Communicator will automatically position the<br />

valve when Relay Adjust is selected.<br />

Rotate the adjustment disc, shown in figure 4‐1, until the output pressure displayed on the Field Communicator is<br />

between 50 and 70% of supply pressure. This adjustment is very sensitive. Be sure to allow the pressure reading to<br />

stabilize before making another adjustment (stabilization may take up to 30 seconds or more for large actuators).<br />

If the low bleed relay option has been ordered stabilization may take approximately two minutes longer than the<br />

standard relay.<br />

43

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!