30.11.2012 Views

WL Circuit Breakers - Siemens

WL Circuit Breakers - Siemens

WL Circuit Breakers - Siemens

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Operating Instructions<br />

<strong>WL</strong> <strong>Circuit</strong> Breaker<br />

Password Protection<br />

All write actions that would result in a<br />

change to the status or a parameter in<br />

the circuit breaker are password protected.<br />

This ensures that parameters cannot be<br />

changed and switching is impossible<br />

without this password.<br />

Note: The electronic relays of the<br />

COM15/COM16 module are required to<br />

open and close the <strong>WL</strong> via the BDA.<br />

The default password is “sentron”<br />

This can be changed by choosing “Extras ><br />

Password” in the BDA tree (recommended).<br />

You have to enter the new password twice.<br />

When you click OK, the BDA asks you for<br />

the old password.<br />

If you have forgotten it, it can be reset<br />

by means of a master password. To<br />

do so, contact Technical Assistance at<br />

1-800-964-4114<br />

info.sea@sea.siemens.com<br />

Operation Example<br />

This example describes the functionality<br />

of the BDA. If you want to set<br />

PROFIBUS/MODBUS address of the<br />

COM15/COM16 module for a <strong>WL</strong> <strong>Circuit</strong><br />

Breaker, open the Communication node<br />

by choosing “Device Parameters > <strong>Circuit</strong><br />

Breaker.” Then click the input/output field<br />

next to the PROFIBUS/MODBUS address<br />

and edit it with the new address. Once<br />

you have changed this parameter and<br />

exited the field, the outline turns blue to<br />

indicate parameters that have not yet been<br />

transferred to the circuit breaker.<br />

You can then change other parameters.<br />

If you want to transfer the modified<br />

parameters to the circuit breaker, click<br />

OK on this page.<br />

If the parameter transfer process is the<br />

first write action in this session, the<br />

system prompts you to enter the password.<br />

Once you have entered the password<br />

successfully, the data is transmitted to the<br />

circuit breaker.<br />

If you want to reset the modified<br />

parameters, click the “Undo” button.<br />

If you exit the parameters page without<br />

clicking OK, the changes are ignored.<br />

Printing<br />

Since Java applets are used, the normal<br />

print function in your browser on the<br />

parameter pages will not provide a<br />

satisfactory printout.<br />

If you want to print the parameters for<br />

documentation purposes, open the pages<br />

to be printed from the tree in the BDA. All<br />

the parameter pages are displayed again<br />

under “Extras > Print,” and you can print<br />

them individually as required using the<br />

print menu in your browser.<br />

Comparing Parameters<br />

The parameter comparison function is<br />

used to check whether the parameters set<br />

with the BDA match those in the device.<br />

The following parameters are checked:<br />

• Protection parameters A and B<br />

• Extended protection function parameters<br />

• Threshold value settings<br />

• Measurement function settings<br />

• Communication parameters<br />

• Settings for the configurable<br />

output module<br />

The parameter comparison function can<br />

be used, for example, to ensure that the<br />

set parameters are transferred without any<br />

errors once they have been downloaded<br />

to the device.<br />

It is not possible to determine whether the<br />

parameters and settings loaded to the<br />

device have actually been transferred.<br />

The reason for this is as follows:<br />

• The BDA just forwards parameter<br />

changes. Whether a parameter is correct<br />

can only be verified in the memory<br />

location (e.g. in the trip unit). If this<br />

changes the value to one that has<br />

exceeded the maximum value, for<br />

example, the modified value is reported<br />

back to the BDA. This discrepancy<br />

would be detected when a subsequent<br />

parameter comparison is performed.<br />

• In the BDA interface, all of the values are<br />

not checked to confirm that they fall<br />

between minimum/maximum values.<br />

There are also other parameters that are<br />

not checked. This means that a parameter<br />

could be entered that cannot be copied<br />

into the trip unit in its current form.<br />

5/25 <strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!