External Power Consumption<br />
<strong>WL</strong> <strong>Circuit</strong> Breaker<br />
The + 24V DC connection must be<br />
connected to X8.3 and the common of<br />
the 24V DC voltage supply must be<br />
connected to X8.4.<br />
Selection criteria for the external power<br />
supply:<br />
• First, the maximum continuous current<br />
which the CubicleBUS modules draw<br />
from the CubicleBUS supply must be<br />
calculated. (see Table 2-23)<br />
• Second, the peak inrush current of all<br />
modules must be calculated. The power<br />
supply must be capable of bearing the<br />
maximum peak inrush current for a<br />
period of 100 ms.<br />
A power supply must be selected in<br />
accordance with these two characteristic<br />
values. Several <strong>WL</strong> <strong>Circuit</strong> <strong>Breakers</strong> can<br />
be connected to one power supply. For<br />
this purpose, however, the total of the<br />
continuous currents must be considered.<br />
For example, the <strong>WL</strong>SITOP1 power supply<br />
can be used with up to 3 ETUs and up to<br />
16 CubicleBUS modules simultaneously.<br />
The <strong>WL</strong>SITOP25 power supply can be used<br />
with two ETUs and up to 8 CubicleBUS<br />
modules simultaneously.<br />
<strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories<br />
Selecting a suitable power supply from the <strong>Siemens</strong> product line<br />
Output current Inrush current Type Order No.<br />
2.5 A < 30 A Logo! Power <strong>WL</strong>SITOP25<br />
3.8 A < 32 A SITOP Power <strong>WL</strong>SITOP1<br />
Table 2-24 A <strong>Siemens</strong> power supply can be selected for one or more <strong>WL</strong> <strong>Circuit</strong> <strong>Breakers</strong>.<br />