Communication with the <strong>WL</strong> Breaker<br />

<strong>WL</strong> <strong>Circuit</strong> Breaker<br />

The <strong>WL</strong> <strong>Circuit</strong> Breaker supports the<br />

industry standard MODBUS protocol<br />

through the COM16 interface.<br />

Communication connections to the<br />

COM16 are made through the DB-9 port<br />

on the front of the COM16; see Graphic<br />

4-2 for connecting cable pin assignments.<br />

Customers can connect twisted shielded<br />

pair RS 485 cable to Ethernet Converters,<br />

MODBUS Masters, PLCs or supervisory control<br />

systems. When the <strong>WL</strong> <strong>Circuit</strong> Breaker is<br />

installed in <strong>Siemens</strong> switchgear as part of<br />

an ACCESS power monitoring system, the<br />

default wiring will be through a <strong>Siemens</strong><br />

power meter Ethernet gateway or Ethernet<br />

converter connected to a WinPM.Net<br />

workstation. For customers with existing<br />

MODBUS networks or who require<br />

Graphic<br />

4-1<br />

WinPM.Net<br />

integration into a MODBUS system the<br />

following information can be used<br />

to develop a software interface to the<br />

<strong>WL</strong> COM16.<br />

Data in the COM16 is organized in what is<br />

referred to as “Datasets.” Each dataset<br />

contains a group of functionally common<br />

registers. For instance all metered data is<br />

organized in a dataset, which consists of<br />

119 registers, min./max. information in<br />

another dataset, and diagnostic information<br />

in another dataset. In all, the COM16 has a<br />

total of 28 datasets, which can be read via<br />

communication. Users can take advantage<br />

of this structure and ask for blocks of data<br />

in one message request, making integration<br />

into MODBUS systems fast and efficient.<br />

The COM16 also supports pre-configured<br />

or standard register maps for simple data<br />

interfacing. Users can define what types<br />

of data they want in any of three default<br />

register sets. Type 1 provides 4 default<br />

registers, Type 2 provides 8 registers, and<br />

Type 3 provides 14 registers, all in<br />

consecutive order for easy requests.<br />

Each register includes a corresponding<br />

status register, which can be read in order<br />

to validate the real-time data. This register<br />

is referred to as the property byte.<br />

The <strong>WL</strong> <strong>Circuit</strong> Breaker can be configured<br />

remotely using the WinPM.Net software or<br />

using the set-up tool, <strong>WL</strong> Config.<br />

<strong>Siemens</strong> Power Monitoring and control software WinPM.Net communicates to multiple device types using Ethernet, modem and RS 485 serial networks.<br />

The integration of the <strong>WL</strong> <strong>Circuit</strong> Breaker into WinPM.Net is a key component of totally integrated power.<br />

4/1 <strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories