Communication with the <strong>WL</strong> Breaker<br />
<strong>WL</strong> <strong>Circuit</strong> Breaker<br />
The <strong>WL</strong> <strong>Circuit</strong> Breaker supports the<br />
industry standard MODBUS protocol<br />
through the COM16 interface.<br />
Communication connections to the<br />
COM16 are made through the DB-9 port<br />
on the front of the COM16; see Graphic<br />
4-2 for connecting cable pin assignments.<br />
Customers can connect twisted shielded<br />
pair RS 485 cable to Ethernet Converters,<br />
MODBUS Masters, PLCs or supervisory control<br />
systems. When the <strong>WL</strong> <strong>Circuit</strong> Breaker is<br />
installed in <strong>Siemens</strong> switchgear as part of<br />
an ACCESS power monitoring system, the<br />
default wiring will be through a <strong>Siemens</strong><br />
power meter Ethernet gateway or Ethernet<br />
converter connected to a WinPM.Net<br />
workstation. For customers with existing<br />
MODBUS networks or who require<br />
Graphic<br />
4-1<br />
WinPM.Net<br />
integration into a MODBUS system the<br />
following information can be used<br />
to develop a software interface to the<br />
<strong>WL</strong> COM16.<br />
Data in the COM16 is organized in what is<br />
referred to as “Datasets.” Each dataset<br />
contains a group of functionally common<br />
registers. For instance all metered data is<br />
organized in a dataset, which consists of<br />
119 registers, min./max. information in<br />
another dataset, and diagnostic information<br />
in another dataset. In all, the COM16 has a<br />
total of 28 datasets, which can be read via<br />
communication. Users can take advantage<br />
of this structure and ask for blocks of data<br />
in one message request, making integration<br />
into MODBUS systems fast and efficient.<br />
The COM16 also supports pre-configured<br />
or standard register maps for simple data<br />
interfacing. Users can define what types<br />
of data they want in any of three default<br />
register sets. Type 1 provides 4 default<br />
registers, Type 2 provides 8 registers, and<br />
Type 3 provides 14 registers, all in<br />
consecutive order for easy requests.<br />
Each register includes a corresponding<br />
status register, which can be read in order<br />
to validate the real-time data. This register<br />
is referred to as the property byte.<br />
The <strong>WL</strong> <strong>Circuit</strong> Breaker can be configured<br />
remotely using the WinPM.Net software or<br />
using the set-up tool, <strong>WL</strong> Config.<br />
<strong>Siemens</strong> Power Monitoring and control software WinPM.Net communicates to multiple device types using Ethernet, modem and RS 485 serial networks.<br />
The integration of the <strong>WL</strong> <strong>Circuit</strong> Breaker into WinPM.Net is a key component of totally integrated power.<br />
4/1 <strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories