Integration into an Automation System<br />

<strong>WL</strong> <strong>Circuit</strong> Breaker<br />

Setting the PROFIBUS Address for the<br />

COM15 Module<br />

The PROFIBUS-DP address is stored in the<br />

COM15 PROFIBUS-DP module on the circuit<br />

breaker. The system is shipped with the<br />

default address 126. All the stations on the<br />

PROFIBUS-DP must have a unique address,<br />

which means that a new address must be<br />

assigned when the PROFIBUS-DP modules<br />

are commissioned.<br />

The COM15 module adopts the new address,<br />

although it cannot be used until the 24V DC<br />

supply voltage for the CubicleBUS has been<br />

interrupted briefly. The address is not active<br />

until the voltage is restored.<br />

<strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories<br />

Figure<br />

3-4<br />

Figure<br />

3-5<br />

SECTION 3<br />

You can also set the communication parameters using the BDA, as well as the parameters<br />

for operation on the Ethernet/intranet/Internet.<br />

You can also use STEP7 to change the PROFIBUS address. To do so, however, the PC with<br />

STEP7 must be connected to the slave by means of an MPI or PROFIBUS interface.<br />