Functional Overview of Trip Unit System<br />
<strong>WL</strong> <strong>Circuit</strong> Breaker<br />
<strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories<br />
P available<br />
– not available<br />
O optional<br />
SECTION 2<br />
Basic Functions ETU748 ETU755 ETU776<br />
Parameter sets<br />
Selectable between<br />
parameter set A and B – P P<br />
LCD<br />
LCD, alphanumeric (4-line) O – –<br />
LCD, graphic – – P<br />
Communication<br />
CubicleBUS integrated P P P<br />
Communication capability via<br />
PROFIBUS/MODBUS P P P<br />
Metering function<br />
Voltage, Power, Harmonics<br />
and Parameterization P P P<br />
Display by LED<br />
Trip unit active P P P<br />
Alarm P P P<br />
ETU error P P P<br />
L trip P P P<br />
S trip P P P<br />
I trip – P P<br />
N trip P P P<br />
G trip P (only with ground fault module) P (only with ground fault module) P (only with ground fault module)<br />
G alarm P (only with ground fault module) P (only with ground fault module) P (only with ground fault module)<br />
Tripped by extended protection or<br />
protective relay function P P P<br />
Communication P P P<br />
Signal contacts with external CubicleBUS modules<br />
(Opto or relay)<br />
Overcurrent warning P P P<br />
Load shedding ON/OFF P P P<br />
Early signal of long-time trip (200 ms) P P P<br />
Temperature alarm P P P<br />
Phase unbalance P P P<br />
Instantaneous trip P P P<br />
Short-time trip P P P<br />
Long-time trip P P P<br />
Neutral conductor trip P P P<br />
Ground fault protection trip P (only with ground fault module) P (only with ground fault module) P (only with ground fault module)<br />
Ground fault alarm P (only with ground fault module) P (only with ground fault module) P (only with ground fault module)<br />
Auxiliary relay P P P<br />
ETU error P P P<br />
2/6