Integration into an Automation System<br />

<strong>WL</strong> <strong>Circuit</strong> Breaker<br />

Graphic<br />

3-2<br />

Stage 1<br />

Read and/or wirte<br />

data sets acyclically<br />

via DPV1 (optional)<br />

Class 1 master<br />

e.g. S7<br />

Stage 1 provides quick and easy access to<br />

the PROFIBUS-DP communication system.<br />

This stage already includes sufficient data to<br />

fulfill most requirements. Communication in<br />

stage 1 is always carried out with a class<br />

1 master.<br />

event driven<br />

diagnostic message<br />

DPV0 cyclic data transmission<br />

Control<br />

Basic type 1<br />

� � � �<br />

Basic type 2<br />

� � � � � � � �<br />

Basic type 3<br />

� � � � � � � � � � � �<br />

3 <strong>WL</strong> <strong>Circuit</strong> Breaker<br />

3<br />

1<br />

or<br />

Class 2 master<br />

e.g. PC<br />

DPV1 C1 channel DPV1 C2 channel Read and/or wirte<br />

data sets acyclically<br />

via DPV1 (optional)<br />

The 3-stage communication concept not only enables quick and easy access, but also ensures that the system can be adapted for more<br />

complex demands. Stage 1 is standard; stages 2 and 3 optional.<br />

The 3-Stage Communication Concept<br />

This concept provides quick and easy access to the PROFIBUS-DP communication system with <strong>WL</strong> circuit breakers.<br />

Stage 2 Stage 3<br />

The cyclic data contains certain predefined<br />

content. It can be changed in the three basic<br />

types and, therefore, easily adapted to<br />

prevailing requirements (e.g. replacing<br />

phase-to-phase voltage with the number of<br />

operating hours). This is an additional option<br />

to stage 1.<br />

or<br />

2<br />

In stage 3, acyclic data records can, if<br />

required, be read or written by a class 1 or<br />

class 2 master. This is useful for requesting<br />

a large volume of data so that it does not<br />

have to be read cyclically (e.g. waveform<br />

buffer data).<br />

3/5 <strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories