Integration into an Automation System<br />
<strong>WL</strong> <strong>Circuit</strong> Breaker<br />
Graphic<br />
3-2<br />
Stage 1<br />
Read and/or wirte<br />
data sets acyclically<br />
via DPV1 (optional)<br />
Class 1 master<br />
e.g. S7<br />
Stage 1 provides quick and easy access to<br />
the PROFIBUS-DP communication system.<br />
This stage already includes sufficient data to<br />
fulfill most requirements. Communication in<br />
stage 1 is always carried out with a class<br />
1 master.<br />
event driven<br />
diagnostic message<br />
DPV0 cyclic data transmission<br />
Control<br />
Basic type 1<br />
� � � �<br />
Basic type 2<br />
� � � � � � � �<br />
Basic type 3<br />
� � � � � � � � � � � �<br />
3 <strong>WL</strong> <strong>Circuit</strong> Breaker<br />
3<br />
1<br />
or<br />
Class 2 master<br />
e.g. PC<br />
DPV1 C1 channel DPV1 C2 channel Read and/or wirte<br />
data sets acyclically<br />
via DPV1 (optional)<br />
The 3-stage communication concept not only enables quick and easy access, but also ensures that the system can be adapted for more<br />
complex demands. Stage 1 is standard; stages 2 and 3 optional.<br />
The 3-Stage Communication Concept<br />
This concept provides quick and easy access to the PROFIBUS-DP communication system with <strong>WL</strong> circuit breakers.<br />
Stage 2 Stage 3<br />
The cyclic data contains certain predefined<br />
content. It can be changed in the three basic<br />
types and, therefore, easily adapted to<br />
prevailing requirements (e.g. replacing<br />
phase-to-phase voltage with the number of<br />
operating hours). This is an additional option<br />
to stage 1.<br />
or<br />
2<br />
In stage 3, acyclic data records can, if<br />
required, be read or written by a class 1 or<br />
class 2 master. This is useful for requesting<br />
a large volume of data so that it does not<br />
have to be read cyclically (e.g. waveform<br />
buffer data).<br />
3/5 <strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories