30.11.2012 Views

WL Circuit Breakers - Siemens

WL Circuit Breakers - Siemens

WL Circuit Breakers - Siemens

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Functions/Parameters for Communications<br />

<strong>WL</strong> <strong>Circuit</strong> Breaker<br />

Setpoints<br />

In addition to the load management option<br />

(load shedding/load restore), the metering<br />

module offers an option for automatic<br />

monitoring of operating data and the<br />

generation of an alarm.<br />

Two setpoints can be defined (e.g., for<br />

overvoltage). With the lower setpoint, an<br />

alarm can be generated via the setpoint<br />

value (e.g. > 480V), whereas, with a<br />

voltage increase, a tripping event (e.g. ><br />

528V) can be generated.<br />

Minimum for Communicated Currents<br />

In order to avoid the detection, display<br />

and communication of very low currents<br />

generated by system noise, even with the<br />

circuit breaker in the disconnect position,<br />

the “Minimum for Communicated Currents”<br />

parameter offers the option of setting all<br />

detected current values smaller than this<br />

parameter to zero. The factory setting is<br />

50A. This means that all values smaller<br />

than 50A are displayed as “0” on the<br />

display, interpreted as “0” for internal<br />

calculations (power) and also transmitted<br />

as “0” via the communications. If this<br />

parameter is changed to “0”, this function<br />

is deactivated and all detected current<br />

measuring values will be directly used.<br />

2/19<br />

The parameter can be found in the parameter<br />

tree of the BDA.<br />

Normal Positive Power Flow Direction<br />

The current direction of the energy “flow”<br />

and the question, “How much energy has,<br />

up to now, flowed in both directions?” is of<br />

particular interest for tie breaker applications.<br />

For a determination, it is important to<br />

define a “normal direction.” This direction<br />

can either be “from top to bottom” or “from<br />

bottom to top.”The measured real power is<br />

either assigned a positive polarity (in<br />

normal direction) or a negative polarity<br />

(opposite of normal direction). In contrast,<br />

the measured currents are always assigned<br />

a positive polarity.<br />

With energy, the transmitted energy values<br />

are incorporated in two counters, real<br />

energy and real energy opposite to normal<br />

direction. The two energy counters are not<br />

assigned a polarity.<br />

Figure<br />

2-7<br />

Event and Trip Log<br />

All events (except for tripping events) are<br />

labeled with a time stamp and an ON (+)<br />

or OFF (-) indication and entered in the<br />

event log.<br />

The event log has a depth of 10 events<br />

and works like a FiFo memory (first in,<br />

first out), i.e. the oldest event is deleted<br />

from the event log upon the occurrence<br />

of a new event.<br />

The trip log is similar to the event log,<br />

however, only the last 5 trips are recorded<br />

with a time stamp and entered in the<br />

trip log.<br />

Note: The event and the trip log are only<br />

available with the COM15/COM16 module.<br />

In the event log the last 10 events on the CubicleBUS are listed. The trip log contains the last 5 trips.<br />

Both of them can be displayed with the BDA.<br />

<strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!