WL Circuit Breakers - Siemens
WL Circuit Breakers - Siemens
WL Circuit Breakers - Siemens
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Diagnostic<br />
<strong>WL</strong> <strong>Circuit</strong> Breaker<br />
Binary Status Information in the<br />
Cyclic Channel<br />
The binary status information in the cyclic<br />
channel is transmitted each time data is<br />
exchanged. The status information is<br />
always identical and always transmitted<br />
at the start of the data message, irrespective<br />
of the basic type that has been selected.<br />
Binary Status Information in the Cyclic Message<br />
Byte Bit <strong>WL</strong><br />
Position of circuit breaker<br />
0 = Disconnected position<br />
0/1 1 = Operating position<br />
2 = Test position<br />
3 = <strong>Circuit</strong> breaker not present<br />
Status of circuit breaker<br />
0 = Not ready<br />
Byte n<br />
2/3 1 = OPEN<br />
2 = CLOSED<br />
3 = Tripped<br />
4 Ready to close<br />
5 Voltage applied to undervoltage release<br />
6 Storage spring is charged<br />
7 Overload warning present<br />
0 An activated setpoint value has been exceeded<br />
1 An alarm signal is currently present<br />
2 PROFIBUS write protection block DPWriteEnable is<br />
activated; write operations are prohibited<br />
3 Status of the free user input on the COM15 module<br />
Reason for last trip<br />
Byte n+1<br />
0 = No trip / last trip acknowledged<br />
1 = Long time (L)<br />
4/5/6<br />
2 = Instantaneous (I)<br />
3 = Short-time (S)<br />
4 = Ground fault (G)<br />
5 = Trip as a result of extended protection function<br />
6 = Overload in neutral conductor<br />
7 Load Shedding warning<br />
Table<br />
3-8<br />
The binary status information is identical in all three basic types, and cannot be changed. It is<br />
transmitted with each message from the circuit breaker. Two bytes provide information on the<br />
most important circuit breaker-related status data.<br />
<strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories<br />
The binary status information comprises<br />
two bytes (not one word, that is, the bytes<br />
do not have to be reversed so that they can<br />
be displayed in Motorola format).<br />
SECTION 3<br />
3/12