Diagnostic<br />
<strong>WL</strong> <strong>Circuit</strong> Breaker<br />
Structure of the PROFIBUS Diagnostic Function<br />
Part of the diagnosis Byte.Bit Meaning for <strong>WL</strong><br />
0 Station status 1<br />
1 Station status 2<br />
DP Standard<br />
2 Station status 3<br />
3 PROFIBUS master address<br />
4 ID no. of high byte (0x80)<br />
5 ID no. of low byte (0xC0)<br />
6 0x42 fixed<br />
ID-related diagnosis<br />
Additional header<br />
Device-specific diagnosis<br />
Table<br />
3-10<br />
<strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories<br />
7<br />
0x00 when no device-specific diagnosis is present<br />
0x01 when a device-specific diagnosis is present<br />
8 0x05 fixed<br />
9 0x82 fixed<br />
10 0x00 fixed<br />
11 0x00 fixed<br />
12 0x00 fixed<br />
13 0x0F fixed<br />
14 0x81 fixed<br />
15 0x01 fixed<br />
16 0x00 fixed<br />
17 0x00 not used<br />
18.0 The COM15 module is not ready for operation<br />
18.1 Not used<br />
State of the main contacts<br />
0= OK<br />
18.2 / 18.3 1 = Perform visual inspection on main contacts<br />
2 = Immediate inspection on main contacts<br />
3 = Not used<br />
18.4 <strong>Circuit</strong> breaker is not present<br />
18.5 –<br />
18.7<br />
Not used<br />
19.0 CubicleBUS not connected<br />
19.1 Not used<br />
19.2 Last action on the CubicleBUS: Module removed<br />
19.3 Last action on the CubicleBUS: Module added<br />
19.4 Last action on the CubicleBUS: Fault detected<br />
19.5 –<br />
19.7<br />
Not used<br />
20.0 – CubicleBUS module, which is removed, added or reports fault<br />
23.7 (19.2 to 19.4)<br />
24.0 –<br />
27.7<br />
Module presence list of the CubicleBUS<br />
SECTION 3<br />
3/16