Functional Overview of Trip Unit System<br />
<strong>WL</strong> <strong>Circuit</strong> Breaker<br />
Data Availability on the CubicleBUS<br />
All modules connected to the CubicleBUS can request data from<br />
other modules via the bus and generate data themselves that can<br />
be read by other modules.<br />
Each data point in the comprehensive <strong>WL</strong> <strong>Circuit</strong> Breaker data<br />
dictionary can only be generated by a single module — the data<br />
source. If this data source (module) exists, the data points assigned<br />
to it also exist.<br />
This information is described and communicated in the<br />
property bytes.<br />
2/7<br />
If a data source (module) does not exist, the data point does not<br />
exist either.<br />
Again, the relevant property byte contains this information.<br />
The following table provides an overview of the internal CubicleBUS<br />
modules and the data point groups (collection of several data<br />
points) assigned to them.<br />
The complete Data Dictionary with a detailed description of the<br />
individual data points is available upon request. Contact your local<br />
sales office.<br />
CubicleBUS Modules<br />
ETU745, 748, BSS COM15/ Metering<br />
Data point group 755 or 776 COM16 Function<br />
Protection parameter set A P<br />
Protection parameter set B (N/A for ETU745 or 748) P<br />
Extended protection parameters P<br />
Parameter for setpoints P<br />
PROFIBUS/MODBUS communication parameters P<br />
Parameters for metering settings P<br />
Device identification data P P<br />
<strong>Circuit</strong> breaker position specifications<br />
Status info. (circuit breaker ON/OFF, open/closed,<br />
P<br />
storage spring, etc.) P<br />
Alarms P<br />
Trip log P P<br />
Setpoint messages P<br />
Maintenance information P P<br />
<strong>Circuit</strong> breaker temperature P<br />
Temperature in the cubicle P<br />
3-phase currents P<br />
Current in neutral, ground-fault current; equip. spec. P<br />
3-phase voltage P<br />
Power KW, KVAR, KVA P<br />
Power factor P<br />
Frequency, total harm. distortion, form factor, crest factor P<br />
Harmonic analysis P<br />
Waveform buffer P<br />
Event log P<br />
System time P<br />
Table The table shows which data points from the data dictionary are generated by which CubicleBUS module, enabling you to quickly find out<br />
2-1 which modules are required for which system.<br />
<strong>WL</strong> PROFIBUS/MODBUS Communication and Electronic Accessories