Set V/F pattern4.10.2 Load pattern selection (Pr. 14)V/FYou can select the optimum output characteristic (V/F characteristic) for the application and load characteristics.ParameterNumberName Initial Value Setting Range Description14 Load pattern selection 00 For constant torque load1 For reduced-torque load2345For constant torque elevators(at reverse rotation boost of 0%)For constant torque elevators(at forward rotation boost of 0%)RT signal on ...for constant torque loadRT signal off ...for constant torqueelevators at reverse rotation boost of 0%RT signal on ...for constant torque loadRT signal off ...for constant torqueelevators at forward rotation boost of 0%Pr.14=0100%Output voltagePr.14=1100%Output voltagePr.14=2Pr.3 Base frequencyOutput frequency (Hz)Pr.3 Base frequencyOutput frequency (Hz)For vertical lift loadsAt forward rotation boost...Pr.0 settingAt reverse rotation boost...0%100%OutputvoltagePr.0ForwardrotationReverserotationBase frequencyOutput frequency (Hz)(1) For constant-torque load (setting "0", initial value)⋅ At or less than the base frequency, the output voltage varies linearly with the outputfrequency.⋅ Set this value when driving the load whose load torque is constant even if the speedvaries, e.g. conveyor, cart or roll drive.POINTIf the load is a fan or pump, select "for rated torque load (setting "0")" in any of thefollowing cases.⋅ When a blower of large moment of inertia (J) is accelerated in a short time⋅ For constant-torque load such as rotary pump or gear pump⋅ When load torque increases at low speed, e.g. screw pump(2) For variable-torque load (setting "1")⋅ At or less than the base frequency, the output voltage varies with the output frequencyin a square curve.⋅ Set this value when driving the load whose load torque varies in proportion to thesquare of the speed, e.g. fan or pump.Pr.14=3For vertical lift loadsAt forward rotation boost...0%At reverse rotation boost...Pr.0 setting100%OutputvoltagePr.0ReverserotationForwardrotationBase frequencyOutput frequency (Hz)(3) Vertical lift load applications (settingvalues "2, 3")⋅⋅⋅Set "2" when a vertical lift load is fixed as power drivingload at forward rotation and regenerative load atreverse rotation.Pr. 0 Torque boost is valid during forward rotation andtorque boost is automatically changed to "0%" duringreverse rotation.Set "3" for an elevated load that is in the driving modeduring reverse rotation and in the regenerative loadmode during forward rotation according to the loadweight, e.g. counterweight system.REMARKS⋅ When torque is continuously regenerated as vertical lift load, itis effective to set the rated voltage in Pr. 19 Base frequencyvoltage to prevent trip due to current at regeneration.144

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!