2WIRINGMain circuit terminal specifications2.2.4 When connecting the control circuit and the main circuit separatelyto the power supply (separate power)MCR/L1 InverterS/L2T/L3R1/L11S1/L21When fault occurs, opening of the electromagnetic contactor (MC) on theinverter power supply side results in power loss in the control circuit,disabling the fault output signal retention. Terminals R1/L11 and S1/L21 areprovided to hold a fault signal. In this case, connect the power supplyterminals R1/L11 and S1/L21 of the control circuit to the primary side of theMC.Remove the jumper1)Remove the upper screws.2)Remove the lower screws.3)Pull the jumper toward you toremove.4) Connect the separate power supplycable for the control circuit to theupper terminals (R1/L11, S1/L21).Never connect the power cable tothe terminals in the lower stand.Doing so will damage the inverter.MCR/L1S/L2 T/L3R1/ S1/L11 L21 Power supplyterminal blockfor the control circuit3)Power supply terminal blockfor the control circuitR1/L11S1/L21Main power supply<strong>FR</strong>-A721-5.5K to 15K<strong>FR</strong>-A741-5.5K to 15K1)2)4)<strong>FR</strong>-A721-18.5K to 55K<strong>FR</strong>-A741-18.5K to 55KPower supplyterminal block forthe control circuitCAUTION· Do not turn off the control power (terminals R1/L11 and S1/L21) with the main circuit power (R/L1, S/L2, T/L3) on. Doing so maydamage the inverter. Make up a circuit which will switch off the main circuit power supply terminals R/L1, S/L2, T/L3 when thecontrol circuit power supply terminals R1/L11, S1/L21 are switched off.· Be sure to use the inverter with the jumpers across terminals R/L1-R1/L11 and S/L2-S1/L21 removed when supplying powerfrom other sources. The inverter may be damaged if you do not remove the jumper.· The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other than theprimary side of the MC.· When separate power is supplied from R1/L11 and S1/L21, the power capacity necessary for the 15K or less is 90VA, for the18.5K or more is 100VA.· If the main circuit power is switched off (for 0.1s or more) then on again, the inverter resets and a fault output will not be held.21

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!