10.12.2012 Views

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

114 <strong>Handbook</strong> <strong>of</strong> <strong>Electrical</strong> <strong>Installation</strong> <strong>Practice</strong><br />

Fig. 5.7 Calculation <strong>of</strong> prospective fault current.<br />

If the Electricity Distributor advises on the fault level at the incoming terminals<br />

the prospective line/earth fault current can be determined at any point on the<br />

site.<br />

The values <strong>of</strong> I f and the voltage drop to the sub-mains positions should be noted<br />

as subsequent calculations and material selection involve these values.<br />

The fault level provides the information necessary to select the protective device<br />

at the main intake position. The breaking capacity rating has already been ascertained<br />

relative to the prospective fault current and it is now necessary to decide the<br />

speed <strong>of</strong> operation <strong>of</strong> the main device.<br />

BS 7671 (the IEE Regulations) stipulates that the maximum disconnection times<br />

under fault conditions are 5 seconds for fixed equipment and 0.4 seconds where the<br />

circuit feeds socket-outlets. However, this latter requirement does not apply to<br />

reduced voltage circuits described in Regulation Group 471-15. Similarly BS 7375:<br />

1996: Distribution <strong>of</strong> electricity on construction and building sites, advises that protection<br />

against earth fault may be obtained in two ways:<br />

(1) By providing a low impedance path to enable the overcurrent device protecting<br />

the installation to operate in a short space <strong>of</strong> time;<br />

(2) By adopting a TT system with residual current device (rcd) and associated<br />

installation earth electrode.<br />

When the earth path is via cable armour as in (1) above and Fig. 5.7, extreme<br />

care is required in protective device selection. The armour impedance may result in<br />

insufficient current flowing to allow the device to trip within the required time, and<br />

changes to specifications do occur; such things as cable routes, equipment positions,<br />

etc. could be revised, and it may be necessary to install a cable with high conductivity<br />

armour, use an additional parallel protective conductor, or provide an rcd as<br />

in (2) above.<br />

The types <strong>of</strong> load can vary enormously, so the area distribution unit needs to be<br />

versatile enough to incorporate a variety <strong>of</strong> final circuit protection devices. The<br />

largest single load is probably the local tower crane where the motors may total<br />

some 80kVA.Various factors need to be considered such as motor starting or dampness,<br />

and because <strong>of</strong> these a final circuit device providing protection against earth<br />

leakage in addition to overcurrent is recommended, particularly if the main site protection<br />

includes earth leakage protection. Careful selection <strong>of</strong> rated tripping current

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!