10.12.2012 Views

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

360 <strong>Handbook</strong> <strong>of</strong> <strong>Electrical</strong> <strong>Installation</strong> <strong>Practice</strong><br />

CIRCUIT-BREAKING<br />

An essential element in the operation <strong>of</strong> any a.c. circuit-breaker is the electric arc,<br />

which permits the current in the circuit to continue flowing after the contacts have<br />

parted, until a suitable current zero occurs. This is illustrated in Fig. 14.1. As will be<br />

described below, the sudden cessation <strong>of</strong> current flow at any time, other than very<br />

close to a natural current zero, has undesirable consequences in all normal distribution<br />

systems, so the existence <strong>of</strong> the arc as a natural commutating device is a very<br />

important factor in the operation <strong>of</strong> a.c. circuit-breakers.<br />

An ideal circuit-breaker is one which acts as a perfect conductor until current<br />

zero is reached, at which point it becomes a perfect insulator.As no practical circuitbreaker<br />

meets this condition, the result is modified to a greater or lesser degree by<br />

the circuit-breaker characteristics. The objective <strong>of</strong> the circuit-breaker designer is<br />

to create the necessary conditions to sweep away the ionisation products in the<br />

contact gap at current zero and replace them by a medium which will withstand the<br />

application <strong>of</strong> a very rapidly rising voltage <strong>of</strong> considerable amplitude, the transient<br />

recovery voltage. This is shown at H in Fig. 14.1.<br />

MEDIUM VOLTAGE SWITCHGEAR<br />

The term medium voltage is usually used to describe switchgear rated from 3.6kV<br />

to 52kV. In the UK it is general practice for m.v. distribution switchgear manufacturers<br />

to supply completely factory-assembled switchgear. This means switchgear<br />

equipment containing busbars and all circuit components up to the cable terminations,<br />

including any switching devices (circuit-breakers, switches, etc.) and their<br />

isolating means. It is, therefore, almost equally general for the switchgear to be<br />

type tested in its completely assembled form. This is not always the case for l.v.<br />

switchgear, since a thriving business exists in this area for the manufacture <strong>of</strong> l.v.<br />

switchboards incorporating circuit-breakers and other l.v. switching devices made<br />

by a small number <strong>of</strong> specialist manufacturers. Also, m.v. circuit-breaker switchgear<br />

is designed principally for use with separately protective relays and therefore has a<br />

short time rating, usually equal to the breaking current rating for three seconds,<br />

unless where very heavy fault levels exist, the operating conditions permit a one<br />

second short time rating. The switch or circuit-breaker also has to be able to close<br />

fully against a short-circuit making current peak equal to 2.5 times the rated breaking<br />

current, and to be able to interrupt that breaking current with a degree <strong>of</strong> asymmetry<br />

which will depend on the opening time <strong>of</strong> the circuit-breaker being<br />

considered. With some <strong>of</strong> the modern high speed circuit-breakers using vacuum or<br />

sulphur hexafluoride (SF 6), this time can be quite short and the d.c. component correspondingly<br />

large. A figure <strong>of</strong> 35% d.c. component is not uncommon under these<br />

circumstances.<br />

All circuit-breakers have to be able to close and open satisfactorily under all conditions<br />

<strong>of</strong> service. In particular they must interrupt all currents from zero to full<br />

rated breaking current with all possible combinations <strong>of</strong> power factor, current asymmetry<br />

and recovery voltage that occur. Figure 14.1 illustrates the typical form <strong>of</strong> the<br />

current and recovery voltage which occurs when a fault current is interrupted. The

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!