392 <strong>Handbook</strong> <strong>of</strong> <strong>Electrical</strong> <strong>Installation</strong> <strong>Practice</strong><br />

Fig. 14.12 Circuit required to test for CT terminal polarity.<br />

circuit a negative ‘flick’ is seen. Where CTs are mounted in transformer bushings it<br />

is necessary to short-circuit the main transformer l.v. winding, thus reducing the<br />

equivalent impedance <strong>of</strong> the transformer to give a good deflection <strong>of</strong> the instrument<br />

needle. Voltage transformers may be checked in similar fashion.<br />

Proving <strong>of</strong> protection<br />

The operation <strong>of</strong> the various forms <strong>of</strong> protection which can be fitted to distribution<br />

switchgear is covered in Chapter 22. Suffice it to say that the operation can be<br />

simulated either by injecting heavy currents through the CT primaries or by the<br />

injection <strong>of</strong> suitably chosen currents into the CT secondary circuits. In some<br />

instances the CTs may be fitted with a special tertiary winding intended for test purposes<br />

in this way. Whichever method is adopted, the intent is to inject currents that<br />

represent fault conditions <strong>of</strong> various types, and to check that the relevant relays<br />

operate correctly and that any auxiliary relays that are called upon to perform do<br />

so also in a correct manner.<br />

To adjust the current settings it is normal to use a variable autotransformer to<br />

provide the supply. As the waveshape <strong>of</strong> the test current can have an influence on<br />

the behaviour <strong>of</strong> the relay it is recommended that as much series resistance as<br />

possible should be included in the injection circuit.<br />

High-voltage tests<br />

If called for in the contract documents h.v. tests can now be applied to the insulation.<br />

The test values should be those be those laid down in the appropriate standard