* Standby earth fault.<br />

Table 22.1 gives a general guide as to the protection suitable for different transformer<br />

ratings, although it should be noted that modern relays such as Duobias M<br />

allow economical protection over the complete range.<br />

Duobias M system<br />

Although Duobias protection, using transductor type relays described above, is used<br />

throughout the world in great numbers, advances in technology have allowed the<br />

development <strong>of</strong> a microprocessor version known as Duobias M (Figs 22.17 and<br />

22.18). This protection incorporates within s<strong>of</strong>tware two restricted earth-fault elements,<br />

models <strong>of</strong> interposing CTs for almost every primary transformer configuration<br />

and inherent phase angle change compensation. The algorithms also include<br />

operation and indication for additional inputs such as Buchholz and winding temperature<br />

protection, and the data storage and fault recording is included.This development<br />

allows an extremely economic but very comprehensive system to be applied<br />

to a full range <strong>of</strong> power transformers.<br />

ROTATING PLANT<br />

Table 22.1 Transformer protection.<br />

Protective Systems 623<br />

The operation <strong>of</strong> rotating machines can be affected by faults within or by external<br />

disturbances on the network. The protection <strong>of</strong> a machine must therefore be<br />

designed to be highly discriminative to react efficiently on internal faults and external<br />

disturbances.<br />

The number and type <strong>of</strong> protective relays applied to a machine is a function <strong>of</strong><br />

the machine characteristics such as size, driving device, single <strong>of</strong> parallel operation,