10.12.2012 Views

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Power Supplies in the UK 15<br />

‘cage’ to someone using an earthed metal appliance in a garden, even though the<br />

appliance may be protected by an RCD (residual current device) in accordance with<br />

the IEE Wiring Regulations. For the same reason metal external meter cabinets are<br />

undesirable.<br />

In order to eliminate as far as possible the chance <strong>of</strong> a completely separated<br />

neutral, a number <strong>of</strong> precautions are taken. First, all cables must be <strong>of</strong> an approved<br />

type with a concentric neutral, either solid or stranded, <strong>of</strong> sufficient current carrying<br />

capacity. Secondly the neutral conductor <strong>of</strong> a spur end on the system is<br />

connected to an earth electrode if more than four consumers’ installations are<br />

connected to the spur, or if the length <strong>of</strong> the spur connection from the furthest connected<br />

consumer to the distributing main exceeds 40 metres. Where reasonably<br />

practicable, cable neutrals are joined together to form duplicate earth connections.<br />

A faulty or broken neutral will give an indication <strong>of</strong> its presence by causing supply<br />

voltages to fluctuate, which, <strong>of</strong> course, should be reported to the local DNO as soon<br />

as possible. All these measures contribute to a system which is as safe as practicable<br />

and self monitoring.<br />

It is the declared intention <strong>of</strong> the EI in the UK to provide earth terminals wherever<br />

required and practicable within the foreseeable future. The local DNO should<br />

be contacted regarding their requirements for the use <strong>of</strong> PME earth terminals for<br />

TN-C-S systems.<br />

High voltage system earthing<br />

The Electricity Supply Regulations specified that every h.v.system shall be connected<br />

with earth at or as near as reasonably practicable to a source <strong>of</strong> voltage in the system.<br />

They also specified that conductors, which respectively connect a supply neutral conductor<br />

with earth and any apparatus used in an h.v. system with earth, shall not be<br />

interconnected unless the combined resistance to earth is 1 W or less; the conductors<br />

shall not be connected to separate earth electrodes unless any overlap between the<br />

resistance areas <strong>of</strong> those electrodes is sufficiently small as not to cause danger.<br />

There are various methods used to earth an h.v. system and practices between<br />

DNOs in the UK vary considerably. Most <strong>of</strong> the 11kV systems are derived from<br />

33/11kV delta star transformers and thus there is a neutral point available. In quite<br />

a number <strong>of</strong> cases these are solidly earthed and the resultant potential earth fault<br />

current can be slightly higher than on a phase-to-phase fault. It is also quite common<br />

to restrict the current by the insertion <strong>of</strong> a resistance or reactance in the neutral<br />

to earth connection to limit the fault current to about the full load <strong>of</strong> the supply<br />

transformer.<br />

Where the h.v. supply is designed directly for 132 or 66kV, it is usual to have a<br />

star wound primary to minimise the transformer cost. In order to get the correct<br />

phase relationship, it is necessary to use a delta secondary winding in some cases<br />

and a star winding in others. When delta secondaries are used it is necessary to<br />

employ a separate earthing transformer to create a star point and this transformer<br />

limits the earth fault current, though frequently a resistor is also used. Where the<br />

secondary winding is star connected, this is either directly connected to earth or<br />

through a resistor. Usually the resistors for this purpose are water-filled but in some<br />

cases a reactor is employed.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!