550 <strong>Handbook</strong> <strong>of</strong> <strong>Electrical</strong> <strong>Installation</strong> <strong>Practice</strong><br />

Fig. 20.3 Cable size selection for cables on trays (single and multi-core cables to<br />

BS 6346).<br />

where Amb = ambient temperature, °C.)<br />

Voltage-drop limit = 6000mV single-phase.<br />

For cable data see Table 20.8. The circuit schedule is given in Table 20.9. A tray<br />

width <strong>of</strong> 450mm has been chosen.<br />

Depth <strong>of</strong> group is then 25916/450 = 57.6mm.