10.12.2012 Views

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

174 <strong>Handbook</strong> <strong>of</strong> <strong>Electrical</strong> <strong>Installation</strong> <strong>Practice</strong><br />

Fig. 7.8 Curves <strong>of</strong> rod resistance with increasing rod radius.<br />

formed a cavity and fissures. Low resistivity material was then introduced into the<br />

cavity and fissures and the earth electrode installed within it. This forms a relatively<br />

large electrode at a lower cost than drilling.<br />

Marconite, concrete or similar materials are also now increasingly used around<br />

structures where these are to be used as part <strong>of</strong> the earthing system.<br />

RESISTANCE MEASUREMENT OF ELECTRODE SYSTEMS<br />

Provided it has sufficient noise immunity (or filtration), the same instrument that is<br />

used for soil resistivity surveys can also be used for measuring the resistance <strong>of</strong> an<br />

earth electrode system. The most common technique used is the ‘fall <strong>of</strong> potential’<br />

test. It should be noted that safety precautions are necessary while carrying out this<br />

test if the earth system is connected to live equipment; for example, fused leads and<br />

an appropriate isolation routine are necessary. This is to ensure that an earth fault<br />

occurring while testing does not subject the individual handling the test probes to<br />

a transferred potential.<br />

Potential and current terminals on the tester are connected to the earth electrode<br />

under test. The remaining current terminal is connected to a current probe which is<br />

inserted into the ground some distance away. The remaining potential terminal is<br />

connected to a voltage probe which is situated at 61.8% <strong>of</strong> the distance between<br />

the current probe and the rod (or centre <strong>of</strong> the earth grid). Current is circulated<br />

between the electrode under test and the current probe, via the current circuit and<br />

the ground. From the voltage detected at the 61.8% position, the apparent resistance<br />

is displayed on the tester. Under ideal conditions, this apparent resistance<br />

reading corresponds to the actual resistance value <strong>of</strong> the earth electrode.The reason<br />

for choosing this position is based on mathematical theory applied to uniform soil.<br />

However, the test electrode and current probe must be sufficiently far away from<br />

the electrode under test that they do not interact. For earth rods the current lead<br />

would be about 100m long and the voltage lead 61.8m. For longer leads the same<br />

ratio must be maintained.<br />

The most common cause <strong>of</strong> error arises from placing the current electrode too<br />

close to the electrode under test. The effects <strong>of</strong> the two electrodes overlap and the

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!