10.12.2012 Views

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

292 <strong>Handbook</strong> <strong>of</strong> <strong>Electrical</strong> <strong>Installation</strong> <strong>Practice</strong><br />

actuator. Care is required to ensure there will be no mechanical failure <strong>of</strong> the<br />

cam plunger mechanism and that failure is limited to a spring breakage or loss<br />

<strong>of</strong> temper. It must not be possible to defeat the interlock without the use <strong>of</strong> tools.<br />

Positive make switches are not suitable because the interlock can be defeated by<br />

operating the switch plunger and, moreover, such a switch can fail to danger if the<br />

spring breaks. Two interlock switches, connected in series, are sometimes used as an<br />

additional precaution.<br />

Test pieces, having no exposed conductors, apart from the ends <strong>of</strong> the leads to be<br />

connected, can be tested on the bench. In this case, the test supply terminals are<br />

enclosed in a box with a hinged lid. When the lid is open, an integral switch opens<br />

the supply circuit, enabling the leads to be connected to the supply terminals which<br />

are usually spring loaded clamps. Closing the lid automatically operates the integral<br />

switch and connects the equipment to the supply. Again, a positive break interlock<br />

switch must be used with a suitable actuating mechanism, to prevent defeat <strong>of</strong> the<br />

interlock feature and to ensure mechanical reliability.<br />

Interlock switches are <strong>of</strong>ten used on doors and the removable panels <strong>of</strong> control<br />

gear where access is required for maintenance and test purposes by electrically<br />

skilled persons. The necessity for this is dubious as such panels should not be openable<br />

without the use <strong>of</strong> a key or tools and so access is restricted to authorised and<br />

competent persons who are well aware <strong>of</strong> the hazards and who will have to defeat<br />

the interlock if they need to carry out ‘live’ testing. However, if such switches are<br />

used, they should preferably be <strong>of</strong> the ‘fail safe’, positive break type and be provided<br />

with a ‘lock <strong>of</strong>f’ facility which can be used if the switch is in a position where<br />

it could be accidentally operated during maintenance or testing.<br />

Other systems<br />

There are two earth free systems called ‘Protection by non-conducting location’ and<br />

‘Protection by earth free local equipotential bonding’, which depend on their locations<br />

being earth free. As it is virtually impossible to guarantee that an earth free<br />

location is always likely to remain so, there is not much scope for these systems in<br />

the UK except for special applications such as the testing <strong>of</strong> radio and television<br />

equipment. However, even then additional precautions are still necessary.<br />

For electronic equipment encased in earthed metal, there is a special highresistance<br />

earthing system for testing, designed to eliminate the shock hazard when<br />

a ‘live’ conductor and the earthed metal case are both touched. The system comprises<br />

a safety isolating transformer, feeding a socket-outlet via a circuit-breaker.<br />

The test piece is connected to the socket-outlet. A centre tapped high resistance is<br />

connected across the circuit-breaker output terminals. The centre point is earthed<br />

via a rectifier bridge and relay coil. If either pole <strong>of</strong> the test circuit is touched when<br />

in contact with the metal case, the fault current is limited by the high resistance to<br />

say 0.50mA which, although insufficient to produce a shock, is enough to operate<br />

the sensitive relay and trip the circuit-breaker (Fig. 11.11).<br />

The principal application <strong>of</strong> energy limitation is in h.v. circuits used in: (1)<br />

TIG welding to ionise the air gap between the electrode tip and the workpiece,<br />

for arc initiation; (2) static elimination, also to ionise the air gap between the<br />

electrode and workpiece and to provide a conducting path for static dispersal; (3)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!