656 <strong>Handbook</strong> <strong>of</strong> <strong>Electrical</strong> <strong>Installation</strong> <strong>Practice</strong><br />

Table 23.8 Recommended sizes <strong>of</strong> fuses and cables for use with capacitors; cables with<br />

copper conductors having thermosetting insulation to BS 5467 (ambient temperature 30°C,<br />

conductor operating temperature 90°C).<br />

Table 23.9 Recommended fuse-switch ratings for use with capacitors at various voltages.<br />

This is especially important in the case <strong>of</strong> capacitors used above 660V where large<br />

derating factors are required. At voltages <strong>of</strong> 3.3kV and 11kV it is not unusual to<br />

find fuses rated at three or four times capacitor current. With such large fuses it<br />

becomes important to ensure that the energy required for correct operation <strong>of</strong> the<br />

fuse is considerably less than the energy required to cause the capacitor tank to