10.12.2012 Views

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

typically consists <strong>of</strong> semiconductor protection installed at board level and gas discharge<br />

tubes installed on the main distribution frame. Certainly this is hardly ever<br />

done in the UK nor, we think, in most other parts <strong>of</strong> the world. If lines are correctly<br />

protected this tends to be true <strong>of</strong> the incoming (PTO) telephone lines only and not<br />

extension lines. These <strong>of</strong>ten travel from building to building and are therefore very<br />

much at risk from lightning.<br />

The use <strong>of</strong> gas discharge tubes alone does not provide adequate protection. The<br />

PBX should be properly protected by devices with a suitably low let-through<br />

voltage.The PBX is an excellent place to install protection because all incoming and<br />

outgoing lines meet at this point.<br />

Choosing and specifying transient overvoltage protectors<br />

In selecting a transient overvoltage protector it is important that the device selected<br />

survives, has a suitable transient control level, and is compatible with the system<br />

it is protecting. It is vital that the protector chosen is capable <strong>of</strong> surviving the<br />

worst case transients expected at its intended installation point. Also, as lightning is<br />

a multiple pulse event, the protector should not fail after exposure to the first<br />

transient.<br />

The protector should be able to control transients to level below the susceptibility<br />

and vulnerability <strong>of</strong> the equipment to be protected; for example, if a computer’s<br />

operation is unhindered by transients <strong>of</strong> up to 700V, then the let-through voltage<br />

or transient control level <strong>of</strong> the protector should be less than 700V. Allowing a<br />

suitable safety margin, the worst case let-through voltage <strong>of</strong> the protector should<br />

be 600V, or less. (Note, the connecting leads <strong>of</strong> a correctly installed protector will<br />

cause an increase in the let-through voltage.) Also the protector should not impair<br />

or interfere with the protected system’s normal operation – something which<br />

communication systems and intrinsically safe circuits are particularly susceptible to.<br />

Location categories<br />

The protector’s ability to survive and to achieve a suitable ‘let-through’ voltage<br />

clearly depends on the size <strong>of</strong> transient to which it will be subjected. This in turn<br />

may depend on the protector’s location. The American Standard IEEE C62.41 and<br />

subsequently BS 6651 outline three location categories.<br />

As a mains-borne transient travels through a building, the amount <strong>of</strong> current it<br />

can source grows smaller (owing to the impedance <strong>of</strong> mains cables and current division).<br />

This is based on the assumption that a typical mains transient caused by lightning<br />

has a 1.2/50ms waveshape.<br />

Location Category C is defined as either:<br />

Lightning Protection 239<br />

• Outside the building, or<br />

• The supply side <strong>of</strong> the main, incoming, l.v. distribution board, i.e. the board bringing<br />

the power supply into the building from the electricity supply authority, l.v.<br />

transformer or from another building, or<br />

• The load side <strong>of</strong> distribution boards providing an outgoing power supply to other<br />

buildings or to on-site equipment.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!