10.12.2012 Views

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

Handbook of Electrical Installation Practice - BeKnowledge

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

296 <strong>Handbook</strong> <strong>of</strong> <strong>Electrical</strong> <strong>Installation</strong> <strong>Practice</strong><br />

(TRS), usually two-core and earth and <strong>of</strong> rectangular section. Many <strong>of</strong> these cables<br />

were used, without further protection, for wiring dwellings and small commercial<br />

properties. In most cases, the rubber has hardened, perished and cracked and when<br />

disturbed falls away exposing the conductors. Short-circuits are then likely to occur<br />

between ‘live’ conductors or to earth and the arcing will sometimes ignite the<br />

remains <strong>of</strong> the insulation and/or anything else flammable nearby.<br />

Other installations have vulcanised rubber insulated (VRI) conductors, taped,<br />

braided and compounded and run in steel conduit. Again the rubber will have perished<br />

but is sometimes retained by the outer covering <strong>of</strong> tape and braid. The hardened<br />

material tends, however, to crack when bent, exposing the conductor. The<br />

conduit protects most <strong>of</strong> the wiring but the exposed ends which are sometimes in<br />

wooden switch boxes or in wooden pattresses supporting switches, socket-outlets or<br />

ceiling roses, are vulnerable and again a short-circuit may occur and the arcing cause<br />

a fire. This old wiring should be replaced by the PVC insulated or insulated and<br />

sheathed equivalents.<br />

Severely overloaded circuits are a fire hazard as the hot conductors damage<br />

the insulation, which will eventually fail and permit a short-circuit to occur.<br />

Examples are sometimes found in old radial socket-outlet circuits where the<br />

DIY operator has sought to increase the supply capacity by replacing old 2 and<br />

5A by double 13A socket-outlets or by adding additional socket-outlets to a<br />

circuit by looping without regard to the size <strong>of</strong> the cable. He then finds that the<br />

protective rewireable fuse on the distribution board is inadequate, and so increases<br />

the size <strong>of</strong> the fuse wire so that the inadequately sized conductors are no longer<br />

protected.<br />

Again, where there are insufficient socket-outlets, adaptors are used and loads, in<br />

excess <strong>of</strong> the rating <strong>of</strong> the socket-outlet, connected. The multiple plugs and<br />

adaptor(s) assembly may not only overload the socket but very <strong>of</strong>ten the socket<br />

receptacles are damaged by the adaptor pins when the assembly is subjected to<br />

lateral pressure from mishandling or a blow. The result is a bad connection, minor<br />

arcing at the contacts, corrosion <strong>of</strong> the surfaces and overheating which ignites the<br />

insulation and anything else flammable nearby. The remedy is to eschew the use <strong>of</strong><br />

adaptors and install an adequate number <strong>of</strong> socket-outlets.<br />

Conductor overheating, resulting in fires, can also occur from loose connections.<br />

Pinch screw terminals in plugs and switches are prone to slacken in time, probably<br />

due to vibration, resulting in bad connections and an eventual fire. Checking terminal<br />

screw tightness should be part <strong>of</strong> the maintenance schedule.<br />

EXPLOSIONS<br />

<strong>Electrical</strong> explosions occur when there is a short-circuit between conductors on different<br />

phases or between a phase conductor and the neutral or earthed metal and<br />

sufficient energy is expended to cause an audible bang. In domestic installations<br />

where the line/neutral and line/earth loop impedances are comparatively high,<br />

usually around 0.3 W to 0.5 W, the short-circuit current will be 230/0.3 or 230/0.5 �<br />

766 or 460A, which is enough to cause an audible bang at the fault location and<br />

at the fuse or circuit-breaker protecting the circuit which clears the fault. Such

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!