Table 20.6 Cable data for singlecore<br />

unsheathed PVC cable in<br />

conduit or trunking.<br />

† Note: All values apply to one singlecore<br />

PVC cable to BS 6004, at 70°C.<br />

rectangular outline <strong>of</strong> the cables is the outline <strong>of</strong> the heat-dissipating surface <strong>of</strong> the<br />

group.<br />

Under these circumstances it is convenient to assume that each cable occupies a<br />

square area with sides equal to the diameter <strong>of</strong> the cable. The total cross-sectional<br />

area <strong>of</strong> the group is then equal to the sum <strong>of</strong> these squares. The depth, calculated<br />

by dividing this area by the width, approximates to the visual depth.The unit system,<br />

used to calculate the area occupied by each circuit, differs therefore from that<br />

used for cables in conduit and trunking by being based on the square <strong>of</strong> the cable<br />

diameter and not on p/4 times that value.<br />

Example 3 Group <strong>of</strong> SWA cables on a perforated steel tray<br />

Ambient temperature 25°C, C a = 1.<br />

(Note: The reference ambient temperature for cables on trays is 25°C, this<br />

being a more usual temperature for industrial installations. For any other ambient<br />

temperature:<br />

C<br />

a =<br />

Ê 70 - Ambˆ<br />

Ë 45 ¯<br />

Selection <strong>of</strong> Wiring Systems 549<br />

Table 20.7 Trunking and conduit data<br />

for groups <strong>of</strong> cables.