Fig. 19.6 600/1000V Waveconal cable (Pirelli Cables Ltd).<br />

Mains Cables 515<br />

are then covered with an extrusion <strong>of</strong> rubber-like material which acts as a bedding<br />

for the concentric neutral conductor, and the same material also completely covers<br />

the wires <strong>of</strong> the neutral conductor.<br />

The aluminium wires forming the neutral conductor (Fig. 19.6) are applied in an<br />

oscillatory manner instead <strong>of</strong> in a helical form and this enables the cores to be<br />

exposed when making tee-joints under live conditions without the need to cut the<br />

neutral wires, and thus break the return path <strong>of</strong> the combined protective and neutral<br />

conductor <strong>of</strong> a TN-C-S system.<br />

The aluminium neutral wires are carefully segregated so that they are individually<br />

surrounded by the rubber-like filling material in order to prevent moisture<br />

transference around the neutral in the event <strong>of</strong> mechanical damage.<br />

The cable is finally sheathed with PVC to provide mechanical protection to the<br />

rubber-like covering around the neutral wires.