Operation and Maintenance Manual for
Operation and Maintenance Manual for
Operation and Maintenance Manual for
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
TROUBLESHOOTING LC <strong>Manual</strong> 11/02 Rev. 3<br />
5.5 LOW SALT REJECTION<br />
A. Verify that the feed water temperature has not increased substantially from<br />
normal. High temperatures can affect percent rejection, as temperature<br />
increases, percent rejection decreases.<br />
B. Check product, reject, reject recycle flow rates <strong>and</strong> feed pressures per the<br />
Equipment Specifications in the Appendix, <strong>and</strong> adjust flows/pressures as<br />
necessary.<br />
C. Another possibility is high CO2 content in the inlet water. CO2 readily permeates<br />
the membrane. High CO2 content water will also have a pH of less than 6.0.<br />
D. RO membrane o-rings may not be seated correctly, check the percent rejection<br />
<strong>for</strong> each individual membrane housing. Remove membranes <strong>and</strong> verify o-rings<br />
are seated correctly on any that are below 90% rejection.<br />
E. If the above possibilities are eliminated, RO membranes are beginning to fail.<br />
They should be cleaned or replaced.<br />
5.6 SYSTEM KEEPS SHUTTING OFF<br />
A. Observe the controller indicators to see if they indicate the cause <strong>for</strong> system<br />
shutdown, if the controller is shutting the unit down refer to the RO controller<br />
section of this manual <strong>for</strong> further discussion.<br />
B. The motor is equipped with automatic thermal overload protection. If the motor<br />
gets too hot it will shut down. After it has cooled it will restart. Excessive amp<br />
draw can cause the motor to get too hot.<br />
C. If an optional sensor is being used (Tank Level switch(es), Pretreatment<br />
Interlock), check to verify the sensor is not shutting off the system.<br />
5.7 SYSTEM SHUTOFF, LOW PRESSURE<br />
A. Verify that the feed water pressure is above 15 psig.<br />
B. Check the differential pressure across prefilter(s). It should be less than 10 psig,<br />
if not replace the prefilter cartridge filter <strong>and</strong> recheck feed pressure.<br />
C. Check the pump suction pressure. It should be greater than 15 psig, if not check<br />
<strong>for</strong> obstruction in piping between the prefilter <strong>and</strong> pump suction.<br />
D. Verify the low pressure switch is operating properly.<br />
5.8 SYSTEM SHUTOFF, HIGH TEMPERATURE<br />
A. Check incoming water temperature.<br />
B. The high temperature shut down is user settable <strong>and</strong> should activate around<br />
35°C ± 3°C (95°F ± 5°F).<br />
C. The temperature thermistor (sensor) is combined in the feed conductivity probe<br />
circuitry. The probe may be replaced if it is giving an erroneous temperature<br />
indication. (Refer to the RO Controller manual in the Appendix <strong>for</strong> correct<br />
values.)<br />
5-2 USFilter