Controls The MC10 is housed in a NEMA 4X enclosure with a membrane keypad. Indicators<br />

include a 4 line x 20 character LCD with LED backlight <strong>and</strong> eight high intensity LED<br />

indicators <strong>for</strong> alarm conditions. The control features of the MC10 are illustrated<br />

below.<br />

Main Menu <br />

Mode=Direct Feed<br />

Hrs Since Start=000<br />

System On<br />

1 2 3<br />

4<br />

CLR<br />

5 6<br />

7 8 9<br />

0<br />

ENT<br />

Main<br />

Menu<br />

LCD Display with Backlight<br />

LOW QUALITY<br />

HIGH TEMP<br />

TANK FULL<br />

CHEM PUMP FAIL<br />

HIGH PRESSURE<br />

LOW PRESSURE<br />

PRETREATMENT OUT<br />

OVERLOAD<br />

SYSTEM START<br />

SYSTEM STOP<br />

ALARM RESET<br />

ALARM SILENCE<br />

LED Alarm <strong>and</strong> Status Indicators<br />

Keys Used <strong>for</strong> Data Entry <strong>and</strong> Configuration<br />

Keypad The membrane keypad contains 20 tactile keys which are used <strong>for</strong> a number of<br />

control <strong>and</strong> data entry functions.<br />

System Start: Pressing this key starts the system. If the Direct Feed mode has<br />

been chosen, pressing the System Start key immediately initiates the<br />

startup sequence. If the Tank Feed mode has been chosen, pressing<br />

this key will not initiate the startup sequence unless the tank is below<br />

high-level. Pressing this key in St<strong>and</strong>-By mode will initiate the flush<br />

sequence of flush cycles.<br />

System Stop: Pressing this key stops the system <strong>and</strong> essentially turns all<br />

functions off.<br />

Keys Used <strong>for</strong> System Control<br />

Alarm Reset: Pressing this key resets the system after an alarm shut down <strong>for</strong><br />

low pressure, high pressure, low quality, high temperature, overload, or<br />

chemical injection failure (VANTAGE RO systems only).