7 Perm Divert TD Sec<br />

8 High Temp SP DegC<br />

9<br />

High Temp DB<br />

DegC<br />

10 High Temp TD Sec<br />

11<br />

12<br />

High Temp Shtdwn<br />

Sec<br />

High Tank Lvl TD<br />

Sec<br />

13 Low Tank Swtch EN<br />

14 Hi Tnk Startup Sec<br />

15<br />

16<br />

17<br />

Low Tank Lvl TD<br />

Sec<br />

High Pressure TD<br />

Sec<br />

Low Pressure TD<br />

Sec<br />

18 Overload TD Sec<br />

19 Pretrt Intlk TD Sec<br />

20* Chem Pump TD Sec<br />

21 Flush Interval Min<br />

22 Flush Duration Sec<br />

23 Feed CND St<strong>and</strong>ard<br />

24 Perm CND St<strong>and</strong>ard<br />

25 Feed Temp Zero<br />

Permeate<br />

Diversion<br />

Time Delay<br />

High<br />

Temperature<br />

Setpoint<br />

High<br />

Temperature<br />

Deadb<strong>and</strong><br />

High<br />

Temperature<br />

Time Delay<br />

High<br />

Temperature<br />

Shut Down<br />

Delay<br />

High Tank<br />

Level Time<br />

Delay<br />

Low Tank<br />

Switch Enable<br />

High Tank<br />

Level Restart<br />

Time Delay<br />

Low Tank<br />

Level Time<br />

Delay<br />

High Pressure<br />

Time Delay<br />

Low Pressure<br />

Time Delay<br />

Overload<br />

Time Delay<br />

Pretreatment<br />

Interlock Time<br />

Delay<br />

Chemical<br />

Pump Failure<br />

Time Delay<br />

Auto Flush<br />

Interval<br />

Auto Flush<br />

Duration<br />

Feed<br />

Conductivity<br />

St<strong>and</strong>ard<br />

Permeate<br />

Conductivity<br />

St<strong>and</strong>ard<br />

Feed<br />

Temperature<br />

Zero<br />

Calibration<br />

* For use with non-medical VANTAGE RO systems only.<br />

(NOT <strong>for</strong> use with Med-RO systems.)<br />

1-255 000 15<br />

0-45 00 32<br />

0.1-10 0.0 3<br />

1-255 000 20<br />

1-255 000 10<br />

1-255 000 5<br />

0 or 1 0 1<br />

1-1000 000 30<br />

1-255 000 5<br />

1-255 000 5<br />

0-255 000 5<br />

1-255 000 2<br />

1-255 000 2<br />

0-100 000 2<br />

1-90 000 60<br />

1-360 000 180<br />

10-3000 0000 NA<br />

0-1000 00.0 NA<br />

1-1500 000 NA<br />

Delay (in seconds) be<strong>for</strong>e the permeate<br />

diversion valve is activated once the<br />

current value falls below the setpoint.<br />

Temperature setpoint (in deg C) which<br />

activates the high temperature alarm.<br />

Deadb<strong>and</strong> (in deg C) through which the<br />

temperature value must pass be<strong>for</strong>e the<br />

high temperature alarm is released.<br />

Delay (in seconds) be<strong>for</strong>e the high<br />

temperature alarm is activated once the<br />

current value rises above the setpoint.<br />

Delay (in seconds) be<strong>for</strong>e the system<br />

shuts down after the high temperature<br />

alarm is activated.<br />

Delay (in seconds) be<strong>for</strong>e the system<br />

shuts down <strong>for</strong> high tank level.<br />

Allows the system to be configured with<br />

or without a low tank level switch. Enter<br />

“1” to enable (low tank level switch<br />

present) or “0” to disable (low tank level<br />

not being used) this feature.<br />

Delay (in seconds) be<strong>for</strong>e the system will<br />

restart after the tank level drops below<br />

the high tank level switch. This feature is<br />

only used when the system is configured<br />

<strong>for</strong> operation without a low tank level<br />

switch.<br />

Delay (in seconds) be<strong>for</strong>e the system<br />

restarts (in Tank Feed mode) when the<br />

level drops below the low tank level<br />

switch.<br />

Delay (in seconds) be<strong>for</strong>e the system<br />

shuts down <strong>for</strong> high pressure.<br />

Delay (in seconds) be<strong>for</strong>e the system<br />

shuts down <strong>for</strong> low pressure.<br />

Delay (in seconds) be<strong>for</strong>e the system<br />

shuts down <strong>for</strong> output overload.<br />

Delay (in seconds) be<strong>for</strong>e the system<br />

shuts down <strong>for</strong> pretreatment interlock.<br />

Delay (in seconds) be<strong>for</strong>e the system<br />

shuts down <strong>for</strong> failure of the chemical<br />

injection pump.<br />

3-5<br />

Interval (in minutes) between autoflush<br />

cycles.<br />

Duration (in seconds) of each autoflush<br />

cycles.<br />

With these settings, the user can<br />

calibrate the conductivity inputs to a<br />

st<strong>and</strong>ard solution. See Calibration<br />

section <strong>for</strong> more in<strong>for</strong>mation.<br />

This setting allows the temperature<br />

sensor in the feed conductivity cell to be<br />

calibrated to zero degrees C. Only<br />

qualified users following the procedures<br />

documented in the Calibration section of<br />

this manual should adjust this setting.