Testing RM Readers<br />

To test the inputs of the RM reader:<br />

17. Press the 6 key to test supervised input number 1.<br />

18. Use resistors across the inputs to simulate the conditions listed in the<br />

following table and check the LED responses.<br />

Table C.1: LED Indications<br />

LED Response<br />

Green LED lights<br />

Amber LED lights<br />

Red LED lights<br />

Red LED flashes slowly<br />

Red LED flashes rapidly<br />

Condition<br />

Input is in secure condition (1K)<br />

Input is in alarm condition (500Ω)/ (2KΩ)<br />

Line fault<br />

Input is open (open)<br />

Input is shorted (shorted)<br />

19. Press the 7 key to test supervised input number 2. The LED responses<br />

indicate the conditions listed in the previous table.<br />

To test the tamper switch of the RM reader:<br />

20. Set SW3-4 (Tamper Override) to OFF (Open)<br />

21. Press the 8 key to test the tamper switch. If the tamper switch is<br />

depressed, the red LED is off. When the switch is released, the red LED<br />

lights up.<br />

Turn off Test Mode:<br />

22. When the RM reader completes the tests, turn off Test Mode by<br />

returning the address switch to its original address setting.<br />