Equipment Wiring Requirements<br />
Equipment Wiring Requirements<br />
Table 2.2: Equipment Wiring Specifications<br />
Table 2.2 lists the wiring requirements for the <strong>apC</strong>/<strong>8X</strong> device and its<br />
components. Consult the Belden specifications for information on<br />
capacitance and resistance.<br />
Signal From To Belden# Gauge # Prs Shielded<br />
Max<br />
Length<br />
RS-232 Comm Host <strong>apC</strong>/<strong>8X</strong> 9855 22 2 Yes 50 ft.<br />
RS-232 Comm<br />
5-wire<br />
Host <strong>apC</strong>/<strong>8X</strong> 8303 22 3 Yes 50 ft.<br />
RS-485 Comm Host <strong>apC</strong>/<strong>8X</strong> 9842** 24 2 Yes 4000 ft.<br />
Comm <strong>apC</strong>/<strong>8X</strong> RM Module 9841 ** 24 1 Yes 4000 ft.<br />
Power <strong>apC</strong>/<strong>8X</strong> RM Module 8442/8461 22/18 1 No Varies<br />
Appendix D<br />
Control Output Strike 8461 18 1 No Varies with<br />
strike draw<br />
Appendix D<br />
Supervised<br />
Input (UL)*<br />
Supervised/<br />
Unsupervised<br />
Input<br />
Input Switch 9462 22 1 Yes 2000 ft.<br />
Input Switch 8442/8461 22/18 1 No 2000 ft.<br />
Request-to-exit Input Switch 8442/8461 22/18 1 No 2000 ft.<br />
Door Contact Input Contact 8442/8461 22/18 1 No 2000 ft.<br />
Relay Control<br />
RM-4,<br />
RM-4DS<br />
ARM-1 9462 22 1 Yes 25 ft.<br />
Reader RM Module Wiegand<br />
Signaling<br />
Read Head<br />
9942<br />
9260<br />
Alpha wire<br />
5386 C<br />
22<br />
20<br />
18<br />
3 Yes 200 ft.<br />
300 ft.<br />
500 ft.<br />
Reader RM Module Magnetic<br />
Signaling<br />
Read Head<br />
22 No 10 ft.<br />
2-4 <strong>apC</strong>/<strong>8X</strong> Installation and Configuration Guide