Wiring Card Readers<br />
<strong>apC</strong>/<strong>8X</strong><br />
Reader<br />
Port<br />
1<br />
2<br />
3<br />
4<br />
+12V<br />
+TXD/+RXD<br />
-TXD/-RXD<br />
GND<br />
Two-wire RS-485 with<br />
shield and drain wire<br />
Reader<br />
1<br />
Reader<br />
2<br />
Reader<br />
3<br />
Reader<br />
4<br />
Reader<br />
5<br />
Reader<br />
6<br />
Last reader must be terminated using<br />
SW3-5 (RM-4) or SW5-5 (RM-4E)<br />
Figure B.2: Connecting the <strong>apC</strong>/<strong>8X</strong> and Readers in a Daisy Chain Configuration<br />
Note:<br />
The last reader in the chain is the one located electrically furthest<br />
from the <strong>apC</strong>/<strong>8X</strong>. In Figure B.2, the last reader in the chain is<br />
Reader 6. Make sure that SW3-5 (RM-4) or SW5-5 (RM-4E) is<br />
closed (On) on Reader 6.<br />
For all RM readers, except the last one in the chain: Make sure switch SW3-5<br />
(RM-4) or SW5-5 (RM-4E) is open (Off).<br />
See Appendix G for detailed wiring diagrams.<br />
<strong>apC</strong>/<strong>8X</strong> <strong>Technical</strong> <strong>Manual</strong> B-5