Wiring Card Readers<br />

Figure B.7: W3 Reader Power Jumper Settings<br />

Up to eight Wiegand signaling readers can be directly wired to the WPSC<br />

using the <strong>apC</strong> internal power supply. If you exceed the rating of the <strong>apC</strong><br />

power supply, you will need to power the readers locally.<br />

• Case A powers all readers with +12 VDC from the <strong>apC</strong> supply.<br />

• Case C powers all readers with +5 VDC from the <strong>apC</strong> supply.<br />

• Case B powers all readers from an external supply through P9.<br />

Note:<br />

The external power supply must be a UL Listed Access<br />

Control (or Burglar Alarm), Class 2, power source.<br />

Caution: To avoid damage to connected readers, make sure that the<br />

P3 power jumper is set correctly for your reader voltage before you<br />

apply power to the <strong>apC</strong>/<strong>8X</strong>.<br />