Wiring Card Readers<br />

Relays 1 through 8 are on the main board; 9 through 16 are on the star coupler.<br />

Relays 17 through 24 are on the MRM, RM-4, or RM-4E; the card readers<br />

activate these relays. See Figure B.15 on page B-23 for details of wiring the<br />

relay outputs.<br />

(normally open)<br />

DC<br />

door lock<br />

(normally closed)<br />

or<br />

secondary<br />

- Local DC + 12 V<br />

relay<br />

(common)<br />

power<br />

Diode - 1N4933 or equivalent<br />

(normally open)<br />

(normally closed)<br />

(common)<br />

MOV - World Products Inc.<br />

SNR-D56K2 or equivalent<br />

Legend<br />

All relays except those on the <strong>apC</strong>/<strong>8X</strong> main board:<br />

Contacts rated for:<br />

Voltage Resistive Inductive<br />

30VDC 2.0A 1.0A<br />

Relays on the <strong>apC</strong>/<strong>8X</strong> main board:<br />

Contacts rated for:<br />

Voltage Resistive<br />

30VDC/AC* 5A<br />

AC<br />

Transformer<br />

Inductive<br />

2.5A<br />

*The output contacts are protected by 36V MOVs,<br />

limiting the connected voltage to 30V.<br />

AC<br />

door lock<br />

or<br />

secondary<br />

relay<br />

Figure B.13: Connecting the Door Locking Mechanism to a Relay<br />

Note:<br />

Normally closed = fail-safe strike<br />

Normally open = fail-secure strike.<br />