Wiring Card Readers<br />
Relays 1 through 8 are on the main board; 9 through 16 are on the star coupler.<br />
Relays 17 through 24 are on the MRM, RM-4, or RM-4E; the card readers<br />
activate these relays. See Figure B.15 on page B-23 for details of wiring the<br />
relay outputs.<br />
(normally open)<br />
DC<br />
door lock<br />
(normally closed)<br />
or<br />
secondary<br />
- Local DC + 12 V<br />
relay<br />
(common)<br />
power<br />
Diode - 1N4933 or equivalent<br />
(normally open)<br />
(normally closed)<br />
(common)<br />
MOV - World Products Inc.<br />
SNR-D56K2 or equivalent<br />
Legend<br />
All relays except those on the <strong>apC</strong>/<strong>8X</strong> main board:<br />
Contacts rated for:<br />
Voltage Resistive Inductive<br />
30VDC 2.0A 1.0A<br />
Relays on the <strong>apC</strong>/<strong>8X</strong> main board:<br />
Contacts rated for:<br />
Voltage Resistive<br />
30VDC/AC* 5A<br />
AC<br />
Transformer<br />
Inductive<br />
2.5A<br />
*The output contacts are protected by 36V MOVs,<br />
limiting the connected voltage to 30V.<br />
AC<br />
door lock<br />
or<br />
secondary<br />
relay<br />
Figure B.13: Connecting the Door Locking Mechanism to a Relay<br />
Note:<br />
Normally closed = fail-safe strike<br />
Normally open = fail-secure strike.<br />
<strong>apC</strong>/<strong>8X</strong> <strong>Technical</strong> <strong>Manual</strong> B-21